Publication 1766-RM001A-EN-P - October 2008
618
Protocol Configuration
Modbus Slave to MicroLogix Memory Map - Detail
Modbus Addressing
Modbus Address Reference
Modbus Function Code (decimal)
0001…4096
Read/Write Modbus Coil Data space
1, 5, 15
10001…14096
Read Only Modbus Contact Data space
2
30001…30256
Read Modbus Input Register space
4
30501
Modbus Data Table Coil File Number
4
30502
Modbus Data Table Contact File Number
4
30503
Modbus Data Table Input Register File Number
4
30504
Modbus Data Table Holding Register File Number
4
30506
Pre-Send Delay
4
30507
Modbus Slave Address
4
30508
Inter-character Timeout
4
30509
RTS Send Delay
4
30510
RTS Off Delay
4
30511
Parity
4
30512
Presentation Layer Error Code
4
30512
Presentation Layer Error Code
4
30513
Presentation Layer Error Count
4
30514
Executed Function Code Error
4
30515
Last Transmitted Exception Code
4
30516
File Number of Error Request
4
30517
Element Number of Error Request
4
30518
Function Code 1 Message Counter - Read Single Output Coil
4
30519
Function Code 2 Message Counter - Read Discrete Input Image
4
30520
Function Code 3 Message Counter - Read Single Holding Register
4
30521
Function Code 4 Message Counter - Read Single Input Register
4
30522
Function Code 5 Message Counter - Set/Clear Single Output Coil
4
30523
Function Code 6 Message Counter - Read/Write Single Holding Register
4
30524
Function Code 8 Message Counter - Run Diagnostics
4
30525
Function Code 15 Message Counter - Set/Clear for Block of Output Coils
4
30526
Function Code 16 Message Counter - Read/Write for Block of Holding Registers
4
30527
Modem Status
4
30528
Total messages responded to by this slave
4
30529
Total messages to this Slave
4
30530
Total Messages Seen
4
30531
Link Layer Error Count
4
30532
Link Layer Error
4
31501…31566
Read Only System Status File
4
40001…40256
Read/Write Modbus Holding Register space (1st Holding Register file).
3, 6, 16