14
MicroLogix 1200 RTD/Resistance Input Module
Publication 1762-IN014B-EN-P - July 2013
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wiring Input Devices to the 1762-IR4
After the module is properly installed, follow the wiring procedure below, using Belden 83503 or
9533 shielded cable.
Wire Type
Wire Size
Terminal Screw Torque
Solid
Cu-90 °C (194°F)
#14…22 AWG
0.904 Nm (8 lb-in.)
Stranded
Cu-90 °C (194°F)
#16…22 AWG
0.904 Nm (8 lb-in.)
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a module
could cause damage at power up. Once wiring is complete, ensure the
module is free of all metal fragments.
cable
signal wire (3)
drain wire
foil shield
signal wires (2)
Cut foil shield and
drain wire
signal wire
signal wire
drain wire
foil shield
cable
signal wires (3)
Cut foil shield and
drain wire