Chapter 4
CIP Axis Attributes
296
Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018
See also
Rockwell Automation Specific Initialization Faults
Standard Initialization Faults
This table defines a list of standard faults associated with the Initialization Faults
attribute.
Standard Initialization Fault Descriptions
Bit
Exception
Description
0
Reserved
This bit cannot be used since the Fault Code is defined by the associated
exception bit number and Fault Code of 0 means no fault condition is
present.
1
Boot Block Checksum Fault
Checksum or CRC error for Boot Block of CIP Motion device detected as part
of Self-Test.
2
Main Block Checksum Fault
Checksum or CRC error for Main Block of CIP Motion device detected as part
of Self-Test.
3
Nonvolatile Memory Checksum
Fault
Checksum or CRC error for NV Memory of CIP Motion device detected as part
of Self-Test.
4...31
Reserved
See also
Rockwell Automation Specific Initialization Faults
Initialization Faults Attributes
This table defines a list of Rockwell Automation specific faults associated with the
Initialization Faults-RA attribute.
Rockwell Automation Specific Initialization Faults Bit Descriptions
Bit
Exception
Description
0
Reserved
This bit cannot be used since the Fault Code is defined
by the associated exception bit number and Fault Code
of 0 means no fault condition is present.
1
Feedback Data Corruption
Smart Encoder Data Corruption detected.
2
Feedback Data Range
Data within a motor data blob is out of range.
3
Feedback Communication Startup
Communications with a smart encoder could not be
established.
4
Feedback Absolute Overspeed
Excessive speed was detected in the battery-backed
encoder while power was off.
5
Feedback Absolute Power Off Travel
The power-off travel range of the battery-backed
encoder has been exceeded.
Standard Initialization Faults
Rockwell Automation Specific
Initialization Faults