Chapter 4
CIP Axis Attributes
204
Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018
Flux Current Feedback
Usage
Access
T
Data
Type
Default
Min
Max
Semantics of Values
Optional - C
Get/GSV
T
REAL
-
-
-
% Motor Rated
Actual flux current applied to the axis based on current sensor feedback.
See also
Current Control Configuration Attributes
These are the Frequency Control Configuration attributes associated with the
Frequency Control method of operation of a Motion Control Axis.
Frequency Control Method
Usage
Access
Data
Type
Default
Min
Max
Semantics of Values
Required - F
Set/GSV
USINT
0
-
-
Enumeration
0 = Basic Volts/Hertz (R)
1...127 = Reserved
128 = Fan/Pump Volts/Hertz (O)
129 = Sensorless Vector (O)
130 = Sensorless Vector Economy
(O)
128...255 = Vendor Specific
The Frequency Control Method attribute identifies the control method
associated with the axis.
The Basic Volts/Hertz control method applies voltage to the motor generally in
direct proportion to the commanded frequency or speed.
Sensorless Vector enhances the Basic Volts/Hertz algorithm by utilizing current
vectors Iq and Id for superior control at low speeds.
Fan/Pump Volts/Hertz is based on the Basic Volts/Hertz but is specifically
tailored for fan/pump applications.
Sensorless Vector Economy applies the Sensorless vector algorithm but seeks to
reduce energy consumption when the applied load is less than 50% of rating.
Frequency Control
Configuration Attributes