Kinetix 5100 I/O Terminal Expansion Block
Install the I/O Terminal Expansion Block
Follow these steps to install your I/O terminal expansion block.
1.
Wire the I/O terminal expansion block, by using the pinout table on page
.
The terminal block accepts the following.
2.
To obtain a high-frequency bond between the cable shield and the expansion block and
for stress relief, firmly attach the cable to the expansion block by using a tie wrap (you
supply).
3.
Attach expansion block to the I/O connector on the front of the Kinetix 5100 drive by
using a screwdriver and torque to 0.2 N•m (1.77 lb•in).
Attribute
2198-TBIO
Wire gauge
1.5…0.05 mm
2
(16…30 AWG)
Strip length
6…7 mm (0.24…0.27 in.)
Torque value
20 N•cm (1.77 lb•in)
Tie Wrap
Exposed copper pad is under
cable shield.
Route wires such that it limits
stress on cable.
I/O
AUX
1