24V dc
FLEX I/O Electronically Fused 8 Output Module
8
&"! %!$# '
2
= Status Indicators (
) – yellow – show status of individual outputs.
= Diagnostic indicators (
) – red – when lit, indicates fault
= Insertable label for writing input designations
= Reset button – press to reset fault
Faults can be reset 3 ways:
•
press the fault reset button
•
toggle the output reset bit (write word 1, bit 08)
•
cycle backplane power
The reset function resets all output fault bits simultaneously. Non-faulted
outputs remain unaffected during the reset
Using the Fault Reset Button
When you press the manual reset button:
•
the fault indicator for the faulted output turns off for about 1.2s (the
faulted output will not attempt to turn on during this delay)
•
after the 1.2s delay, the faulted output attempts to turn on
•
if the external condition causing the fault is corrected, the output will
remain on, the fault indicator is off, and the status indicator is on