Publication 1794-6.5.11 - November 1997
5-12
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Word 7
cont.
Bits 08-11
(10-13)
Minimum Frequency Sampling Time (channel 1) – Specifies the minimum time (in ms) the module will spend collecting
pulses to determine the Frequency.
Bit
11
(13)
10
(12)
09
(11)
08
(10)
Minimum Frequency Sampling Time – in ms
0
0
0
0
2
0
0
0
1
4
0
0
1
0
5
0
0
1
1
10
0
1
0
0
20
0
1
0
1
50
0
1
1
0
100
0
1
1
1
200
1
0
0
0
500
1
0
0
1
1000
1010 to 1111 not used – 2ms default sample time used
Bit 12 (14)
Invert Select – Frequency Input (channel 1) – Selects whether to invert the Frequency input signal, if not using an Active High
(24V = On) 24 Vdc IEC 1+ sensor or “Normally Open” relay or switch contact on the 24 Vdc Frequency Input terminal. Allows
compatibility with an Active Low (0V = On) 24 Vdc IEC 1+ sensor or “Normally Closed” relay contact on the 24 Vdc Frequency
Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On).
Default
= 0 – Normal (Active High, 24V = On)
Bit 13 (15)
Invert Select – Gate Input (channel 1)
–
Selects whether to invert the Gate input signal, if not using an Active High (24V = On)
24 Vdc IEC 1+ sensor or “Normally Open” relay or switch contact on the 24 Vdc Gate Input terminal. Allows compatibility with
an Active Low (0V = On) 24 Vdc IEC 1+ sensor or “Normally Closed” relay contact on the 24 Vdc Gate Input terminal.
0 = Normal (Active High, 24V = On),
1 = Invert input (Active Low, 0V = On)
Default
= 0 – Normal (Active High, 24V = On)
Bit 14 (16)
Wire Off Fault Select – Frequency Input (channel 1) – Selects whether to turn On or Off the 24 Vdc Frequency input IEC 1+
hardware Wire Off (Lead Breakage) detection. NOTE: Customer devices must draw more than 0.4 mA in the On and Off State.
To use this feature with relays or switches, connect a “shunt resistor” (~ 50K) across the contacts.
0 = Disable,
1 = Enable
Default
: = 0 – Disable
Bit 15 (17)
Wire Off Fault Select – Gate Input (channel 1) – Selects whether to turn On or Off the 24 Vdc Gate input IEC 1+ hardware Wire
Off (Lead Breakage) detection. NOTE: Customer devices must draw more than.4 mA in the On and Off State. To use this
feature with relays or switches, connect a “shunt resistor” (~ 50K) across the contacts.
0 = Disable,
1 = Enable
Default
= 0 – Disable
Word 8
Bits 00-15
(00-17)
Reserved
Word
Bit
Definition
Содержание FLEX I/O 1794-IJ2
Страница 1: ...User Manual FLEX I O Frequency Input Module Cat No 1794 IJ2 Allen Bradley Allen Bradley Replacements ...
Страница 6: ...Publication 1794 6 5 11 November 1997 4 Using This Manual ...
Страница 19: ...Publication 1794 6 5 11 November 1997 1 10 Overview of the Frequency Input Module Allen Bradley Replacements ...
Страница 38: ...Publication 1794 6 5 11 November 1997 3 6 Programming Your Frequency Input Module ...
Страница 67: ...Publication 1794 6 5 11 November 1997 6 4 Troubleshoot the Frequency Input Module Allen Bradley Replacements ...