14
FLEX I/O 5V DC TTL Digital Input and Output Modules
Publication 1794-IN119C-EN-P - August 2018
General Specifications
Attribute
Value
Terminal base screw torque
Determined by installed terminal base
Dimensions, approx. (H x W x D)
94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in.)
Weight, approx.
76 g (2.68 oz.)
Indicators (field side)
16 yellow status indicators
External DC power supply voltage, nom 5V DC
External DC power voltage range
4.5...5.5V DC (includes 5% AC ripple)
External DC supply current range
210 mA @ 5V DC –
1794-IG16
100 mA @ 5V DC –
1794-OG16
North American temp code
T4A
Keyswitch position
1
Enclosure type rating
None (open-style)
Wire size
Determined by installed terminal base
Wiring category
(1)
(2)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
1770-4.1
.
(2)
Use this Conductor Category information for planning conductor routing as described in the appropriate System Level
Installation Manual.
(1794-IG16)
3 - on signal ports
2 - on power ports
(1794-OG16)
2 - on signal ports
At the end of its life, this equipment should be collected separately from any
unsorted municipal waste.