    FLEX Ex 24V dc Non-Isolated Source 4 Output Module 

Publication

 1797-5.6 - December 2003

Field Descriptions

Analog/Digital Output Mode

Selects if the channel acts as a normal analog output 
or as a switched digital output.

Analog Output Mode will follow the Analog Data 
Format selected.

Digital Output Mode will output 0mA = OFF, 22mA = 
ON if the Fault Mode is 0 = disable. Digital Output 
Mode will output 2mA = OFF, 22mA = ON if the Fault 
Mode is 1 = wire off fault detection enabled.

Range: 0 = normal analog output, 1 = switched digital 
output.

Analog Output Data

Specifies the value of the analog output data to the 
module. Specific format is controlled by Module Data 
Format Control parameter. This data is used when the 
channel is in analog output mode.

Digital Output Data

Specifies the value of the digital output data to the 
module. This data is used when the channel is in 
digital output mode.

Range: 0 = output, 0mA = OFF, 1 = 22mA = ON if the 
Fault Mode is 0 = disable. 0 = output, 2mA = OFF, 1 = 
22mA = ON if the Fault Mode is 1 = wire off fault 
detection enabled.

Global Reset

This bit acts to reset all outputs to accept normal 
system output data. It acts in conjunction with the 
Latch Retry parameter. If any channel faults occur, the 
Latch Retry parameter can be set to cause the fault to 
be latched and the output to go to its safe state 
value.

This is an edge triggered signal. It must first be set to 
the “1” state, reset will then occur on the “1” to “0” 
transition.

Содержание FLEX Ex 1797-OB4D

Страница 1: ...equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages...

Страница 2: ...n and understanding of the product ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you iden...

Страница 3: ...nal base 5 Press firmly and evenly to seat the module in the terminal base unit The module is seated when the latching mechanism 7 is locked into the module ATTENTION This equipment is considered Grou...

Страница 4: ...one 1 This module must not be exposed to the environment Provide a suitable metal enclosure This module has a protection factor of IP20 Installation on Zone 22 When the module is installed in Zone 22...

Страница 5: ...e system against electrostatic charge Post a sign near this module Attention Avoid electrostatic charge For your convenience a sign which can be cut out is included in this installation instruction Re...

Страница 6: ...ility EMC Part 6 2 Generic Standards Immunity for Industrial Environments EN61326 1997 A1 A2 Electrical Equipment For Measurement Control and Laboratory Use Industrial EMC Requirements ATEX Directive...

Страница 7: ...connected to each other Wiring to a 1797 TB3 or TB3S Terminal Base Unit Connect wiring to the terminal base as shown below 1 Connect the individual output wiring to terminals 0 4 8 12 on the 0 15 row...

Страница 8: ...nal 50 V on this base unit to terminal 34 on the next base unit 6 If continuing common to the next terminal base unit connect a jumper from terminal 51 V on this base unit to terminal 35 on the next b...

Страница 9: ...le such as bus bars and shield terminating feed throughs Output Output Output Output 0 A 0 A 1 Output 1 A 4 A 5 Output 2 A 8 A 9 Output 3 A 12 A 13 V C 34 and C 50 V C 35 and C 51 ATTENTION Do not use...

Страница 10: ...e power up check is running B Insertable labels for writing individual input designations C Power Indicator green indicates power applied to module Memory Mapping Dec Bit 15 14 13 12 11 10 09 08 07 06...

Страница 11: ...to the factory Where O Output OVL Overload alarm for individual channel FS Fault state 0 is reset and 1 is hold last state FM Detection of output faults 0 is disable and 1 is enable L Latch alarms 0...

Страница 12: ...Detection Fault bits in data table and LED per channel blinking red 1 Hz Electronic Protection Lead break overload short circuit Maximum Output Delay Times OFF to ON ON to OFF 1 2ms 1 2ms Indicators...

Страница 13: ...ns Operational Temperature 20 to 70o C 4 to 158o F Storage Temperature 40 to 85o C 40 to 185o F Relative Humidity 5 to 95 noncondensing ShockOperating Tested to 15g peak acceleration 11 1 ms pulse wid...

Страница 14: ...c format is controlled by Module Data Format Control parameter This data is used when the channel is in analog output mode Digital Output Data Specifies the value of the digital output data to the mod...

Страница 15: ...e information contained in the Module Safe State data until the value is set to 1 when normal function continues Analog Fault State Determines how module reacts to faults when channel is used in analo...

Страница 16: ...h Retry Mode Latch Retry determines channel operation under wire off fault conditions These bits control the action of two channel groups channels 0 3 and or channels 4 7 When a channel fault occurs t...

Страница 17: ...mechanism primarily targets fault behavior for loss of network communication Program Mode Behavior The adapter also monitors the state of the controlling processor or scanner Two states can be detect...

Страница 18: ...utput depending upon the module type This mechanism primarily targets fault behavior for loss of backplane communication Power Up State Behavior The system and modules use the Output Enable bit at sys...

Страница 19: ...f Electrical Equipment for Use in Hazardous Classified Locations UL 2279 Electrical Equipment for Use in Class I Zone 0 1 and 2 Hazardous Classified Locations UL 508 Industrial Control Equipment CSA C...

Страница 20: ...each channel is separated in accordance with the National Electric Code NEC or Canadian Electric Code CEC Table 1 Wiring Method Channel Terminals Voc V Isc mA Vt V It mA Groups Ca F La mH 1 and 2 Any...

Страница 21: ...Entity Concept parameters of Voc 5 8V Isc 400mA To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc 9 5V Isc 1A To any IS device with Entity Concept paramete...

Страница 22: ...ble and Li Lcable respectively for the intrinsically safe apparatus Simple apparatus is defined as a device which neither generates nor stores more than 1 2V 0 1A 20 J or 25mW Wiring methods must be i...

Страница 23: ...1 Hazardous Classified Locations FM C1 No 3615 1989 Explosionproof Electrical Equipment General Requirements FM C1 No 3810 1989 1995 Electrical and Electronic Test Measuring and Process Control Equip...

Страница 24: ...base may or may not have an I O module installed 1797 OB4D Allen Bradley B A 0 1 2 3 4 5 6 7 PWR 7 4 Point Source Output Module FLEX Ex Discrete Output I O Module LEDs Female Bus Connection Field Wiri...

Страница 25: ...to the General FM Certification Information on page 29 1 of 1797 6 5 6 From FM approved devices 1797 PS2N For connection to other modules refer to the General FM Certification Information on page 29 1...

Страница 26: ...values of Ca and La of the associated apparatus are greater than Ci Ccable and Li Lcable respectively for the intrinsically safe apparatus Simple apparatus is defined as a device which neither genera...

Страница 27: ...2003 Output Voltage Current Capability IMPORTANT For detailed certification information refer to the FLEX Ex System Certification Reference Manual publication 1797 6 5 6 Voltage mA 30 25 20 15 10 5 0...

Страница 28: ...support rockwellautomation com Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation please review the information that s contained in t...