DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 15
Publication 1790-IN012C-EN-P - January 2015
Interpret the Status Indicators
Read this section for information about how to interpret base block status indicators. The
base block has these status indicators:
•
Block status
•
Network status
•
I/O status
If a module status indicator is flashing red, refer to the cable break procedures section.
Status Indicators
Indicator
Status
Description
Module
Solid red
Unrecoverable fault in base unit.
Replace base block.
Flashing red
Fault in expansion unit, or
Node address switches do not match current node
address.
Reconnect or replace, as needed.
Solid green
Normal operation.
Off
No power.
Apply power to device.
Network
Solid red
Module node number is a duplicate of an existing
node, or network communication issues exist.
Change module node number to an unused address, or
verify network wiring is correct and communication is
stable.
Flashing red
An I/O connection has timed out.
Cycle power to the module.
Solid green
The module is operating in a normal condition, and the
module is online with connections in the established
state. As a group 2 module, the module is allocated to
a master.