32
ControlNet-to-DeviceNet Linking Device
1788-5.2B - October 1999
CSA Hazardous Location Approval
Hazardous Location Approval
This product is certified for general use as well as for use in hazardous locations.
Actual
agency certification is indicated by the product label
as shown below, and not by
statements in any user documentation.
The certification label:
To comply with certification for use in hazardous locations, the following information becomes
a part of the product literature for this certified industrial control product.
•
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or
non-hazardous locations only.
•
The products having the appropriate markings (that is, Class I, Division 2, Groups A, B, C,
D) are certified for use in other equipment where the suitability of combination (that is,
application or use) is determined by the local authority having jurisdiction.
Important:
Due to the modular nature of a programmable control system, the product with the
highest temperature rating determines the overall temperature code rating of a programmable
control system in a Class I, Division 2, location. The temperature code rating is marked on the
product label as shown.
Temperature code rating:
The following warnings apply to products having certification for use in hazardous locations.
ATTENTION:
Explosion hazard -
•
Substitution of components may impair suitability for Class I, Division 2.
•
Do not replace components unless power has been switched off or the
area is known to be non-hazardous.
•
Do not disconnect equipment unless power has been switched off or the area is known to
be non-hazardous.
•
Do not disconnect connectors unless power has been switched off or the area is known to
be non-hazardous. Secure any user-supplied connectors that mate to external circuits on
this equipment by using screws, sliding latches, threaded connectors, or other means
such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for
a minimum of one minute.
CL I, DIV 2
GP A,B,C,D
TEMP
CL I, DIV 2
GP A,B,C,D
TEMP