Allen-Bradley ControlNet 1788-CNCR Скачать руководство пользователя страница 3

ControlNet Daughtercard     

7

Publication 1788-IN002C-EN-P - April 2004

Setting the Node Address

You must set two switch assemblies to configure the daughtercard with its unique network 
address. Figure 1 shows the location of the switches. These switches are read on powerup to 
establish the network address of the card.

Set the node address to a value between 01 and 99. For optimum throughput, assign 
addresses to your ControlNet nodes in a sequential order starting with 01.

Node address 00 is not a valid ControlNet address. You should only use node address 00 if 
the product that uses the ControlNet daughtercard has the ability to set the node address 
using the host device interface.

This feature is typically used on products that do not allow easy customer access to the node 
address switches. If you set the node address switch to 00, it allows the host in which the 
daughtercard resides to set the node address, rather than allowing the daughtercard to read 
the node address from the switch settings.

Figure 1  Setting the Node Address

31044-M

I/O 

 

status 

 

LED

module

 

status 

 

LED

NAP

node address 
switches

                      network status indicators (A and B)

                    network status indicators (A and B)

channel A connector

channel A connector

channel B connector

Содержание ControlNet 1788-CNCR

Страница 1: ...to a ControlNet network you should also refer to these publications ControlNet Tap Installation Instructions publication 1786 5 7 ControlNet Coax Media Planning and Installation Guide publication CNE...

Страница 2: ...88 CNC or CNCR card can keep the network parameters at any legal node address 01 to 99 Multiple devices on any one network can act as the network keeper Each device capable of being the network keeper...

Страница 3: ...ress You should only use node address 00 if the product that uses the ControlNet daughtercard has the ability to set the node address using the host device interface This feature is typically used on...

Страница 4: ...ices we cannot provide specific performance capabilities in this document For information concerning host daughtercard performance characteristics refer to the user manual for the particular host devi...

Страница 5: ...Coax Tap Installation Instructions publication 1786 5 7 ControlNet Coax Media Planning and Installation Guide publication CNET IN002 See page 14 for information about status indicators IMPORTANT If y...

Страница 6: ...rk access port NAP using another cable could result in possible network failures or product damage The NAP port is for temporary local programming purposes only and not intended for permanent connecti...

Страница 7: ...Fc Operating 5g 10 500Hz Operating Shock IEC 60068 2 27 Test Ea Unpackaged Shock 30g Non Operating Shock IEC 60068 2 27 Test Ea Unpackaged Shock 50g Emissions CISPR 11 Group 1 Class A ESD Immunity IEC...

Страница 8: ...munity EN 61000 6 4 Industrial Emissions C Tick 3 Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EEx 3 European Union 94 9 EC ATEX Directive compliant with EN 5...

Отзывы: