Publication
1756-IN016B-EN-P - November 2003
PN 957824-46
Supersedes Publication 1756-IN016A-EN-P - October 2000
Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Surge Transient
Immunity
IEC 61000-4-5:
+2kV line-earth (CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Enclosure Type Rating
None (open-style)
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment
for Class I, Division 2 Group A,B,C,D
Hazardous Locations
FM
FM Approved Equipment for use in Class
I Division 2 Group A,B,C,D Hazardous
Locations
CE
(4)
European Union 89/336/EEC EMC
Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab.,
Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
(4)
Australian Radiocommunications Act,
compliant with:
AS/NZS CISPR 11; Industrial Emissions
EEx
(4)
European Union 94/9/EEC ATEX
Directive, compliant with:
EN 50021; Potentially Explosive
Atmospheres, Protection “n” (zone 2)
(1)
Maximum wire size requires extended housing - 1756-TBE.
(2)
Use this conductor category information for planning conductor routing as described in the system
level installation manual.
(3)
Refer to publication 1770-4.1
Industrial Automation Wiring and Grounding Guidelines
.
(4)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.