    ControlLogix TTL Input Module 

Publication

 1756-IN584B-EN-P - August 2003

Removal and Insertion Under Power

Be sure that power is removed or the area is nonhazardous before 
proceeding. Repeated electrical arcing causes excessive wear to 
contacts on both the module and its mating connector. Worn contacts 
may create electrical resistance that can affect module operation.

North American Hazardous Location Approval

!

WARNING

When you insert or remove the module while backplane 
power is on, an electrical arc can occur. This could cause 
an explosion in hazardous location installations.

The following information applies when 
operating this equipment in hazardous 
locations:

Informations sur l’utilisation de cet équipement 
en environnements dangereux :

Products marked “CL I, DIV 2, GP A, B, C, D” are 
suitable for use in Class I Division 2 Groups A, B, 
C, D, Hazardous Locations and nonhazardous 
locations only. Each product is supplied with 
markings on the rating nameplate indicating the 
hazardous location temperature code. When 
combining products within a system, the most 
adverse temperature code (lowest “T” number) 
may be used to help determine the overall 
temperature code of the system. Combinations 
of equipment in your system are subject to 
investigation by the local Authority Having 
Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu’à une utilisation en environnements de 
Classe I Division 2 Groupes A, B, C, D dangereux et 
non dangereux. Chaque produit est livré avec des 
marquages sur sa plaque d’identification qui indiquent 
le code de température pour les environnements 
dangereux. Lorsque plusieurs produits sont combinés 
dans un système, le code de température le plus 
défavorable (code de température le plus faible) peut 
être utilisé pour déterminer le code de température 
global du système. Les combinaisons d’équipements 
dans le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de 
l’installation.

Содержание ControlLogix 1756-IG16

Страница 1: ...ookstore com and place an order call 800 963 9548 USA Canada or 001 320 725 1574 outside USA Canada To See page Identify the Module Components 6 Note the Power Requirements 7 Understand the Low True F...

Страница 2: ...ublication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation office describes some important differences b...

Страница 3: ...nclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply w...

Страница 4: ...tions only Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code When combining products within a system the most adverse temperature code l...

Страница 5: ...in an area known to be nonhazardous AVERTISSEMENT RISQUE D EXPLOSION Couper le courant ou s assurer que l environnement est class non dangereux avant de d brancher l quipement Couper le courant ou s a...

Страница 6: ...odule uses one of the following RTBs 1756 TBNH 20 position NEMA RTB 1756 TBSH 20 position Spring Clamp RTB Use an extended depth cover 1756 TBE for applications with heavy gauge wiring or requiring ad...

Страница 7: ...a low true format Inputs may be in the ON or OFF state depending on the voltage applied to the input 0 2V to 0 8V dc Input guaranteed to be in ON state 0 8 to 2 0V dc Input state not Guaranteed 2 0 to...

Страница 8: ...wear to contacts on both the module and its mating connector Worn contacts may create electrical resistance that can affect module operation 1 Align the circuit board with the top and bottom chassis...

Страница 9: ...module that correspond to unkeyed positions on the RTB For example if you key the first position on the module leave the first position on the RTB unkeyed 1 To key the module insert the U shaped band...

Страница 10: ...G When you connect or disconnect the Removable Terminal Block RTB while field side power is on an electrical arc can occur This could cause an explosion in hazardous location installations 20863 M Spr...

Страница 11: ...IN 5 IN 7 DC 0 IN 0 IN 2 IN 4 IN 6 DC COM 0 IN 9 IN 11 IN 13 IN 15 DC 1 IN 8 IN 10 IN 12 IN 14 DC COM 1 NOTES 1 We recommend you use this diagram for applications that do not require CE compliance For...

Страница 12: ...DC 1 IN 8 IN 10 IN 12 IN 14 DC COM 1 GENERAL NOTES 1 We recommend you use Belden 8761 cable where shielded cables are shown 2 Do not connect more than two wires to any single terminal 3 This example...

Страница 13: ...module is unlocked WARNING When you connect or disconnect the Removable Terminal Block RTB with field side power applied an electrical arc can occur This could cause an explosion in hazardous location...

Страница 14: ...f the module Use the following information to remove the module if necessary Indicator Displaying Means Take this action OK Steady green light The inputs are being multicast and in normal operating st...

Страница 15: ...odule WARNING When you insert or remove the module while backplane power is on an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is remov...

Страница 16: ...Current 4 1mA maximum Input Impedance 1 4K minimum 1 5k typical Low True Format The module operates with the following definitions of ON and OFF states 0 2V to 0 8V dc Input guaranteed to be in ON st...

Страница 17: ...clamp 7 to 9 inch pounds 0 8 to 1Nm maximum Module Keying Backplane Software configurable RTB Keying User defined mechanical keying Conductors Wire Size Category 22 to 14 AWG 0 324 to 2 08 sq mm stran...

Страница 18: ...hock 30g Non Operating Shock IEC60068 2 27 Test Ea Unpackaged shock 50g Emissions CISPR 11 Group 1 Class A ESD Immunity IEC 61000 4 2 4kV contact discharges 8kV air discharges Radiated RF Immunity IEC...

Страница 19: ...ntrol Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions C Tick 4 Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions 1 T...

Страница 20: ...http support rockwellautomation com Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation please review the information that s contained...

Отзывы: