Analog I/O Wiring Diagrams

All analog I/O commons (ANLG COM) are connected in the analog I/O card of the 
packaged controller. The analog common (ANLG COM) is not connected to earth 
ground inside the packaged controller.

Analog I/O channels are not isolated from each other.

Use Belden 8761 (or equivalent) shielded wire.

Under normal conditions, the drain wire and shield junction must be connected to earth 
ground via a panel or DIN rail mounting screw at the analog I/O removable terminal 
block end. Keep the shield connection to ground as short as possible.

To ensure optimum accuracy, limit overall cable impedance by keeping your cable as 
short as possible. Plan to place the packaged controller as close to your sensors or 
actuators as your application permits.

(1)

If multiple power supplies are used with analog inputs:

the power supply commons must be connected.

do not exceed the specified isolation voltage.

The embedded analog I/O does not provide loop power for analog inputs. Use a power 
supply that matches the input transmitter specifications.

Differential analog inputs are more immune to noise than single-ended analog inputs.

Voltage outputs (Vout 0+ and Vout 1+) of the analog I/O are referenced to ANLG 
COM. Load resistance for a voltage output channel must be equal to or greater than 1 
K

.

Current outputs (Iout 0+ and Iout 1+) of the analog I/O source current that returns to 
ANLG COM. Load resistance for a current output channel must remain between 
0…300 

.

Voltages on Vin+, V/Iin-, and Iin+ of the analog I/O must be within 0 to +10V DC of 
analog common.

ATTENTION: 

Analog outputs may fluctuate for less than a second when power is applied or 

removed. This characteristic is common to most analog outputs. While the majority of loads will 
not recognize the short signal, take preventive measures to ensure that connected equipment is 
not affected.

IMPORTANT

In environments where high-frequency noise may be present, it may be necessary to directly 
ground cable shields to earth at the removable terminal block end and via a 0.1μF capacitor at 
the sensor end.

(1)

Cable length over 50 m (164.04 ft) may impact accuracy. For details, refer to the Compact Combination Analog I/O Module, publication

 

1769-UM008

.

Содержание CompactLogix 1769-L23-QBFC1B

Страница 1: ...ules optional 12 Panel Mount the System 14 DIN rail Mount the System 14 Grounding Considerations 15 Wiring Power to the System 15 Wire the I O Removable Terminal Blocks 17 Connect Using the RS 232 Con...

Страница 2: ...r installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respec...

Страница 3: ...ent or minimize the spread of flame complyingwithaflamespreadratingof5VA V2 V1 V0 orequivalent ifnon metallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sect...

Страница 4: ...le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst me sont sujettes inspection p...

Страница 5: ...al Health and Safety Requirements has been assured by compliance with EN 60079 15 and EN 60079 0 WARNING This equipment must be installed in an enclosure providing at least IP54 protection when applie...

Страница 6: ...expansion I O modules you can add total the bus current draw maximum of your planned expansion I O modules and the end cap If your result is less than IMPORTANT The series B controllers are compatibl...

Страница 7: ...ackaged controller you may choose to use these components specific to your application Planned Expansion I O Module Bus Current Draw max 1 1 The maximum bus current draw specification for each Compact...

Страница 8: ...23E QB1B 1769 L23E QBFC1B and 1769 L23 QBFC1B 1769 ECR Compact right end cap 1769 L23E QB1B 1769 L23E QBFC1B and 1769 L23 QBFC1B 1769 RDQB CompactLogix packaged controller door 1769 L23E QB1B 1769 RDQ...

Страница 9: ...agedControllerDimensions 1769 L23E QB1BPackagedController The 1769 L23E QB1B controller has these approximate dimensions Measurement Dimension approximate a 185 2 mm 7 29 in b 123 86 mm 4 88 in c 118...

Страница 10: ...aged controllers have these approximate dimensions Measurement 1 1 Applies to both the 1769 L23E QBFC1B and 1769 L23 QBFC1B packaged controllers Dimension approximate a 249 25 mm 9 81 in b 123 86 mm 4...

Страница 11: ...t side of the packaged controller 2 Carefully attach the battery connector to the port located inside the packaged controller 3 Insert the battery wires down in the slot on the battery door WARNING Wh...

Страница 12: ...les optional If using expansion modules with your packaged controller complete these steps to attach the modules 1 Remove the end cap by unlocking it and sliding it forward 2 Align the tongue and groo...

Страница 13: ...the locking tab on the top of the module 5 If using another expansion module complete steps 2 4 for the second module 6 Align the tongue and groove slots of the end cap with those on the right of the...

Страница 14: ...nting tabs on the packaged controller and expansion modules if used and tighten DIN railMounttheSystem To mount your system on a DIN rail complete these steps The packaged controller can be mounted on...

Страница 15: ...or DIN rail if used are not required unless the mounting surface cannot be grounded Refer to the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 for additional information...

Страница 16: ...d I O must be powered from a source compliant with one of the following safety extra low voltage SELV protected extra low voltage PELV Power Wire Size and Terminal Screw Torque Wire Type Wire Size Ter...

Страница 17: ...d cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding ATTENTION Mis wiring the removable terminal blocks to an AC power s...

Страница 18: ...inking I O circuits are driven by a current sourcing field device Field devices connected to the negative side DC Common of the field power supply are sinking field devices Field devices connected to...

Страница 19: ...ut Source describes the current flow between the I O and the field device Sourcing output circuits supply source current to sinking field devices Field devices connected to the negative side DC Common...

Страница 20: ...power for analog inputs Use a power supply that matches the input transmitter specifications Differential analog inputs are more immune to noise than single ended analog inputs Voltage outputs Vout 0...

Страница 21: ...LG Com ANLG Com V out 1 I out 1 V out 0 I out 0 Earth ground the shield locally at the module Differential Voltage Transmitter Belden 8761 Cable or equivalent V in 0 V I in 0 I in 0 V in 1 V I in 1 I...

Страница 22: ...t 1 V I in 3 I in 3 Single ended Voltage Transmitter Differential Voltage Transmitter Differential Current Transmitter 2 wire Current Transmitter Signal Signal Signal Signal Supply Analog I O Terminal...

Страница 23: ...roperly grounded using these guidelines This product is intended to be mounted to a well grounded mounting surface such as a metal panel Additional grounding connections from the packaged controller s...

Страница 24: ...proper cable type The type of cable used should be twisted pair individually shielded cable with a maximum length of 300 m 1000 ft A A B B Z Z A1 A1 B1 B1 Z1 Z1 GND VS VDC COM Cable 1 Power Supply Al...

Страница 25: ...ly voltages To calculate the maximum resistor value use this formula Where R maximum pull up resistor value VDC power supply voltage Vmin 2 6V DC Imin 6 8 mA The minimum resistor R value depends on th...

Страница 26: ...a Where R maximum pull up resistor value VDC power supply voltage Vmin 2 6V DC Imin 6 8 mA The minimum resistor R value depends on the current sinking capability of the sensor Refer to your sensor s d...

Страница 27: ...s Foradditionaldetails refer to Industrial Automation Wiring and Grounding Guidelines Allen Bradley publication 1770 4 1 2 Sourcing Output Source describes the current flow between the I O and the fie...

Страница 28: ...he controller WARNING If you connect or disconnect the serial cable with power applied to this module or the serialdeviceontheotherendofthecable anelectricalarccanoccur Thiscouldcauseanexplosion in ha...

Страница 29: ...dded I O EDS files are available on the RSLogix 5000 software version 17 CD at http support rockwellautomation com and at http www ab com networks eds DownloadPackagedControllerFirmware Packaged contr...

Страница 30: ...ed controller project 3 Click RSWho to specify the controller path 4 Select your packaged controller and click Download You may also choose to click Update Firmware to complete this process If you do...

Страница 31: ...13 6 Use the checkbox and pull down to select your controller and firmware revision 7 Click Update 8 Click Yes The firmware upgrade begins IMPORTANT Do not interrupt the firmware upgrade once it has b...

Страница 32: ...the firmware upgrade you see the status change as shown below Continue to allow the firmware upgrade to complete without interruption When the firmware upgrade is complete the Download dialog box dis...

Страница 33: ...e packaged controller and click Next 5 Expand the network until you see your packaged controller and select it 6 Click OK 7 Choose the revision level to which you want to update the packaged controlle...

Страница 34: ...re upgrade begins During the firmware upgrade you see the status change as shown below Continue to allow the firmware upgrade to complete without interruption IMPORTANT Do not interrupt the firmware u...

Страница 35: ...y and delete tasks programs or routines Stoptheexecution scanning oftasks Thatis thepackagedcontrollerdoesnotexecute orscan tasks while the keyswitch is in the Prog position When the keyswitch is in t...

Страница 36: ...dicators display acomplexsequenceofvaryingredandgreenstates Thissequenceindicatesthepower upself test and takes approximately 1 2 minutes for the packaged controller to complete Controller Status Indi...

Страница 37: ...ler keyswitch from PROG toRUN to PROG Go online with RSLogix 5000 software Anonrecoverablemajorfaultoccurredonthepackagedcontroller Inthiscase the packaged controller a OK indicator initially displays...

Страница 38: ...een The port is operating correctly Normal operation no action is required Steady red The packaged controller is holding the port in reset or the packaged controller has faulted Clear the fault If the...

Страница 39: ...nfigured check connection originator for connection error code Steady green The port has an IP address and CIP connections Class 1 or Class 3 are established Normal operation No action is required Ste...

Страница 40: ...n the left side of each CompactLogix packaged controller Indicator Status Description DCH0 Off Channel 0 configuration differs from the default serial configuration Steady green Channel 0 has the defa...

Страница 41: ...the indicator is green the analog I O have power have passed internal diagnostics and are communicating properly If analog I O OK indicator is off a fault is present High speedCounterStatusIndicators...

Страница 42: ...Specifications Technical Data publication 1769 TD005 Controller specifications CompactLogix Packaged Controllers Quick Start and User Manual publication IASIMP QS010 Procedures for using your Compact...

Страница 43: ...CompactLogix Controller 43 Rockwell Automation Publication 1769 IN082C EN P February 2013 Notes...

Страница 44: ...r for initial help in getting your product up and running NewProductSatisfactionReturn Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from th...

Отзывы: