Field Wiring Connections
System Wiring Guidelines
Consider the following when wiring your system:
General
•
Route field wiring away from any other wiring and as far as
possible from sources of electrical noise, such as motors,
transformers, contactors, and ac devices. As a general rule, allow
at least 15.2 cm
(6 in.) of separation for every 120V of power.
•
Routing field wiring in a grounded conduit can reduce electrical
noise.
•
If field wiring must cross ac or power cables, ensure that they
cross at right angles.
•
If multiple power supplies are used with analog millivolt inputs,
the power supply commons must be connected.
Terminal Block
•
Do not use the module’s NC terminals as connection points.
•
For millivolt sensors, use Belden 8761 shielded, twisted-pair wire
(or equivalent) to ensure proper operation and high immunity to
electrical noise.
•
For a thermocouple, use the shielded, twisted-pair thermocouple
extension lead wires specified by the thermocouple manufacturer.
Using the incorrect type of thermocouple extension wire or not
following the correct polarity will cause invalid readings.
•
To ensures optimum accuracy, limit overall cable impedance by
keeping a cable as short as possible. Locate the module as close to
input devices as the application permits.
Содержание CompactBlock LDX 1790D-4T0
Страница 1: ...CompactBlock LDX I O Thermocouple Modules 1790D T4T0 1790D 4T0 1790P T4T0 User Manual AB Drives ...
Страница 2: ......
Страница 8: ...Publication 1790 UM003A EN P May 2002 viii ...
Страница 50: ...Publication 1790 UM003A EN P 3 20 Module Data Status and Channel Configuration for DeviceNet ...
Страница 56: ...Publication 1790 UM003A EN P 4 6 Diagnostics and Troubleshooting ...
Страница 102: ...Publication 1790 UM003A EN P G 4 ...
Страница 108: ...Publication 1790 UM003A EN P May 2002 I 6 ...
Страница 111: ...AB Drives ...