    ArmorBlock 2-Port EtherNet/IP Module 

Publication 1732E-IN004C-EN-E - May 2012

Depending on the devices used, it may be possible to provide power through only one pair 
of the four available pins, and in this case the other available pair may be used for single 
channel E-stop through the use of special E-stop drop or power T-ports and shorting 
plugs. Allen-Bradley E-stop T-ports and shorting plugs are red in color for 
easy identification. 

Configure the Module

Refer to the illustration for configuration operations.

Configure Operations

ATTENTION: 

To comply with the CE Low Voltage Directive (LVD), this 

equipment and all connected I/O must be powered from a source compliant 
with the following:

 

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

ATTENTION: 

If any I/O device connected to this equipment requires Class 2 

power to operate, this equipment and all connected I/O must be powered by a 
Class 2 source.

LINK 1

LINK 2

EtherNet/IP D-Code 

M12 connector

Network address

 

 switches

Auxiliary power

44945

Eight M12 I/O 

connectors

EtherNet/IP D-Code 
M12 connector

Содержание ArmorBlock 1732E-16CFGM12R

Страница 1: ...M12DR Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 Overview 4 Catalog Number Explanation 6 Install the Module 6 Set the Network Address 6 Mount the Module 7 Product Dimensions 8 Connect the I O Network and Auxiliary Cables to the Module 9 Configure the Module 12 Interpret LED Indicators 13 Specifications 15 ...

Страница 2: ...nstallation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is pr...

Страница 3: ...nimize the spread of flame complying with a flame spread rating of 5VA V2 V1 V0 or equivalent if nonmetallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications In addition to this publicat...

Страница 4: ...opriate enclosure I O connectors are sealed M12 style EtherNet IP networks use advanced network technology for example producer consumer communication to increase network functionality and throughput Resource Description Pinout Guide for 1732 ArmorBlock 2 Port Ethernet Block publication 1732E WD001 Detailed description of how to wire your module 1732E EtherNet IP ArmorBlock supporting Sequence of ...

Страница 5: ...nectors See I O Connectors on page 9 2 Functional Earth grounds the I O block s EtherNet IP communication circuitry which is designed to mitigate the effect of noise on the network See EtherNet IP Connector on page 10 44945 LINK 1 LINK 2 Status LEDs Auxiliary power Functional Earth 1 Nodeaddress switches Protective Earth 2 EtherNet IP D Code M12 connector EtherNet IPD Code M12 connector M12 I O co...

Страница 6: ...he switches first to determine if the switches are set to a valid number To set the network address 1 Rotate the three 3 switches on the front of the module using a small blade screwdriver Catalog Number Description Network Connector Auxiliary Power 1732E IB16M12R 16 Channel 24V DC Digital Input Dual Port EtherNet Module Dual D code M12 Single 4 pin mini 1732E OB16M12R 16 Channel 24V DC Digital Ou...

Страница 7: ... have a host name assigned to it or use any Domain Name Server If the switches are set to an invalid number for example 000 or a value greater than 254 excluding 888 the I O block checks to see if DHCP is enabled If DHCP is enabled the I O block asks for an address from a DHCP server The DHCP server also assigns other Transport Control Protocol TCP parameters If DHCP is not enabled the I O block u...

Страница 8: ...ule in High Vibration Areas If you mount the module in an area that is subject to shock or vibration we recommend you use a flat and a lock washer to mount the module Mount the flat and the lock washer as shown in the mounting illustration Torque the mounting screws to 1 13 Nm 10 in lb LINK 1 LINK 2 44946 43 25 mm 1 70 in 26 5 mm 1 04 in 65 mm 2 56 in 179 mm 7 05 in 169 mm 6 65 in Front view Side ...

Страница 9: ...ule Connect the quick disconnect cord sets you selected for your module to the appropriate ports I O Connectors Refer to the pinout diagrams for the I O connectors Micro style 5 Pin Input Female Connector Micro style 5 Pin Output Female Connector 44766 Lock washer Flat washer 1 2 4 5 3 44807 View into connector Pin 1 Sensor source voltage Pin 2 Input B Pin 3 Return Pin 4 Input A Pin 5 PE 1 2 4 5 3...

Страница 10: ...ections against leaks and maintain IP enclosure and NEMA type requirements 1 2 4 5 3 View into connector Pin 1 Sensor source voltage Pin 2 Input or output B Pin 3 Return Pin 4 Input or output A Pin 5 PE 44807 Output scan list Turn output on Output circuit Sensor or actuator Connector pin Input is on or output is on Input circuit 43601 Input scan list From PLC To PLC 4 2 3 1 5 View into connector P...

Страница 11: ...Male Receptacle Auxiliary Power is based on a 4 pin connector system and is used to provide 24V DC power to I O modules and other devices Running separate power to these devices is most typically used for I O devices with output connections to prevent power supply interruption due to switching of outputs However some devices require separate auxiliary power to power them regardless of the presence...

Страница 12: ...tion Configure the Module Refer to the illustration for configuration operations Configure Operations ATTENTION To comply with the CE Low Voltage Directive LVD this equipment and all connected I O must be powered from a source compliant with the following Safety Extra Low Voltage SELV or Protected Extra Low Voltage PELV ATTENTION If any I O device connected to this equipment requires Class 2 power...

Страница 13: ...lable at www rockwellautomation com en e tools Interpret LED Indicators This module has the following indicators Network Module and Link status indicators for EtherNet IP Auxiliary Power indicator Individual I O status indicators for inputs and outputs LINK 1 LINK 2 Link status indicator Module status indicator I O status indicator Link status indicator Module status indicator I O status indicator...

Страница 14: ...hing red One or more connections have timed out Red The module has detected that its IP address is already in use Flashing red green The module is performing a powerup self test Network link status Off No link established Green Link established on indicated port at 100 Mbps Flashing green Link activity present on indicated port at 100 Mbps Yellow Link established on indicated port at 10 Mbps Flash...

Страница 15: ...urrent on state input max 5 mA 30V DC Voltage sensor source max 30V DC Voltage sensor source min 10V DC Input delay time ON to OFF OFF to ON 0 16000 μs Isolation voltage 50V continuous Basic Insulation Type Inputs and Sensor Power to Network No isolation between individual Inputs or between Network channels Type tested at 707V DC for 60 s 1732E ArmorBlock 2 Port EtherNet Module Output 1732E 8X8M12...

Страница 16: ...tween Outputs and Output power or between Network channels Type tested at 707V DC for 60 s General Specifications Attribute Value Voltage auxiliary power max 30V DC Voltage auxiliary power min 12V DC Current Ethernet system power max pins 2 3 sensor source module power 0 4 A 1732E OB16M12R 1732E OB16M12DR 0 8 A 1732E 8X8M12DR 1 2 A 1732E IB16M12R 1732E IB16M12DR 1732E IB16M12SOEDR 1732E 16CFGM12R ...

Страница 17: ...1 on power ports 1 on communications port 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Environmental Specifications Attribute Value Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 60 C 4...

Страница 18: ...lse 100 AM 900 Mhz 10V m with 200 Hz 50 Pulse 100 AM 1890 Mhz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 4 kV 5 kHz on power ports 3 kV 5 kHz on signal ports 3 kV 5 kHz on communications ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports 2 kV line earth CM...

Страница 19: ...ments EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A B C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EtherNet IP ODVA conformance tested to EtherNet IP specifications KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Ac...

Страница 20: ...operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature United ...

Отзывы: