12
Rockwell Automation Publication 1732E-UM001A-EN-P - December 2019
Chapter 2
Configure and Startup
Configure the Module
The module supports Implicit Messaging and Explicit Messaging for
EtherNet/IP communication.
Use Implicit Messaging to transfer I/O process data cyclically through assembly
objects and an existing connection.
Use Explicit Messaging to transfer data with low priority, non time-critical, and
configuration and through acyclical messages.
Connections and Assembly Objects
The module uses the connection types Data and Listen Only for exchanging I/O
process data and communication through Implicit Messaging.
By selecting the corresponding instance ID of the assembly object, you can decide
how many items of I/O process data the module makes available to the user.
The ArmorBlock I/O 16-channel configurable digital module provides the
following connections and assembly IDs:
Configuration Parameters
To transfer the configuration parameters, the module uses different assembly
objects depending on the module type. See
Connections and Assembly Objects
for more information.
Each module has a fixed number of configuration parameters. This variable is
determined by the respective configuration assembly instance.
Length of the configuration parameters is 65 words (130 bytes).
Table 2 - Profile for ArmorBlock I/O 16-channel Configurable Digital Module
Connection Type
Diagnostics
Assembly ID
Length
Data
Yes
Output: 100
2 bytes
Input: 101
7 bytes
Configuration: 110
130 bytes
Listen Only
Yes
Output: 192
0 bytes
Input: 101
7 bytes
Configuration: N/A
N/A