Publication 1732D-IN001B-EN-E - May 2004
DeviceNet 1732 ArmorBlock I/O, Series A
3
Install Your ArmorBlock
I/O Module
To install the module:
•
Set the node address
•
Mount the module
•
Connect the cord sets
•
Attach the network cables
•
Communicate with the module
Set the Node Address
Valid node addresses are
00
through
63
.
Set the node address using either the rotary switches, RSNetWorx for
DeviceNet
, DeviceNetManager
, or another software configuration
tool. Setting the switches at any number from
64
to
99
lets the
software have address control.
Each module is shipped set for node address
63
. Remove the caps on
the front of the module to access the switches. The two switches are:
•
X10 (most significant digit) - left side of module
•
X1 (least significant digit) - right side of module
To reset the node address, use a small blade screwdriver to rotate the
switches. Line up the small black dot on the switch with the number
setting you wish to use and then cycle power.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge,
which can cause internal damage and affect normal
operation. Follow these guidelines when you handle
this equipment:
•
Touch a grounded object to discharge potential
static.
•
Wear an approved grounding wriststrap.
•
Do not touch connectors or pins on component
boards.
•
Do not touch circuit components inside the
equipment.
•
If available, use a static-safe workstation.
•
When not in use, store the equipment in
appropriate static-safe packaging.