857-VPA3CG Profibus DP Option Module
Specifications
General
PROFIBUS Cable
PROFIBUS devices are connected in a bus structure. Up to 32 stations (master or
slaves) can be connected in one segment.
The bus is terminated by an active bus terminator at the beginning and end of
each segment (see
Cabling Bus Termination on page 11
). To ensure error-free
operation, both bus terminations must always be powered. When more than 32
stations are used, repeaters (line amplifiers) must be used to connect the
individual bus segments.
The maximum cable length depends on the transmission speed and cable type.
The specified cable length is increased by the use of repeaters. The use of more
than three repeaters in series is not recommended.
Table 2 - PROFIBUS DP Connections
Interface
9-pin DSUB connector (female)
Transfer method
RS-485, Half-duplex
Transfer cable
Twisted-pair (1 pair and shield)
Electrical
500V DC
Safety
Meets standard EN50178
Table 3 - PROFIBUS Communication Data
Communication mode
PROFIBUS DP
Communication parameters
Address
1…126
Baud Rate
9.6 kBaud...12 MBaud
Table 4 - Line Parameters
Parameter
Line A
Line B
Impedance
135...165 Ω (3…20 MHz)
100…130 Ω
(f> 100 kHz)
Capacity
< 20 pF/m
< 60 pF/m
Resistance
110 Ω/km
—
Wire gauge
> 0.64 mm (22 AWG)
> 0.53 mm (24 AWG)
Conductor area
> 0.34 mm
2
(22 AWG)
> 0.22 mm
2
(24 AWG)
Table 5 - Line Lengths for Different Transmission Speeds
Baud rate (bBit/s)
9.6
19.2
93.75
187.5
500
1500
3000…12,000
Length Line A (m)
1200
1200
1200
1000
400
200
100
Length Line B (m)
1200
1200
1200
600
200
—
—