background image

Pressure Switch  836T 

– Allen Bradley 

 

Control Setting 

— Style T Pressure Controls

 

 

Allen-Bradley controls are designed for ease of setting to help minimize installation time. Standard 

pressure controls shipped from the factory are set at the maximum operating range and minimum 

differential. By using a pressure gauge and following these simple directions, the control can be set to 

the specific requirements for each application. See (Figure 5).

 

 

Step 1 — Adjust trip setting

 

The trip setting is controlled by the operating range adjustment screw and is adjusted externally. After 

loosening the lock nut, the trip setting is set by turning the operating range adjustment screw 

counterclockwise to lower the trip setting or clockwise to raise the trip setting. The approximate trip 

setting is shown on the indicating scale. When the proper setting is reached, simply tighten the lock 

nut. 

 

Note:

 Turning the operating range adjustment screw will cause both the trip and reset settings to 

change in virtually equal increments. 

 

Step 2 — Adjust reset setting

 

The reset setting is controlled by an external differential adjustment screw. The reset setting is set by 

turning the differential adjustment screw clockwise to increase the differential or counterclockwise to 

decrease the differential.  

Note:

 Adjusting the differential has little or no affect on the trip setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание 836T

Страница 1: ...tween trip and reset Max occasional surge pressure Maximum surge pressure that can be applied to the actuator Surges or transients can occur during start up and shut down of a machine or system Expressed in milliseconds complex electronic instrumentation is required to measure the varying amplitude frequency and duration of this wave form Extreme surges that occur approximately 8 times in a 24 hou...

Страница 2: ...and 3 8 in N P T female pipe threads SAE 7 16 and SAE 9 16 O ring boss seals are also available piston versions only Contact configuration Bulletin 836T controls are available with either a 2 circuit or 4 circuit contact block See Contacts Style D Style D pressure difference controls adjustable system difference range The adjustable operating range for a pressure difference control System differen...

Страница 3: ...s are designed to open or close electrical circuits in response to changes in pneumatic air or gas or hydraulic oil or non corrosive liquids pressure Piston controls are not intended for use with air or water Figure 2 shows the basic operating mechanism Pressure is applied to the actuator which can be either a bellows or piston type As pressure rises the actuator exerts force on the main spring Wh...

Страница 4: ...ses and contacts return to their normal state this is referred to as reset setting Varying the force of the main spring by turning the operating range adjustment screw determines when the contacts will trip Varying the force of the differential spring by turning the differential adjustment screw determines when the contacts will reset Setting trip and reset values determines the operating paramete...

Страница 5: ...Figure 3 shows a typical control application Here pressure is controlled within predetermined high and low values Figure 4 shows a typical monitoring application Here pressure is monitored between a high and low value signaling when a preset limit has been exceeded Figure 3 Typical Control Application Figure 4 Typical Monitoring Application ...

Страница 6: ...ening the lock nut the trip setting is set by turning the operating range adjustment screw counterclockwise to lower the trip setting or clockwise to raise the trip setting The approximate trip setting is shown on the indicating scale When the proper setting is reached simply tighten the lock nut Note Turning the operating range adjustment screw will cause both the trip and reset settings to chang...

Страница 7: ...tment for pressure controls Mounting without Removing Cover Bulletin 836T controls can be mounted without removing the front cover This helps prevent foreign materials from entering the opened enclosure during the interval between mounting and wiring of the control ...

Отзывы: