Non-display Solid-state Pressure Transmitter

Dimensions [mm (in.)]

1/4 in. NPT Female

1/4 in. NPT Male

Process Connection

Commissioning

Making the Mechanical Connection

• While mounting, make sure that the sealing faces at the instrument and the measuring point are clean and undamaged.
• Only screw or unscrew the instrument via the spanner flats and to the prescribed torque with an appropriate tool. The correct torque 

depends on the dimensions of the process connection and the gasket used (form/material). When screwing or unscrewing the pressure 

transmitter, do not use the housing as contact surface. 

• Be careful not to cross-thread.
•  Max torque is 50 N•m (442.54 lb•in).

Mating Cables

Process Connection 

889D-F4AC-2 (M12x1 connector)

Measuring Cell 

Piezoresistive measuring cell and metallic measuring diaphragm

889D-R4AC-2 (M12x1 right angle connector)

Application

Measurement and monitoring of absolute and gauge pressures

Process connection

Thread

− 1/4 NPT female

− 1/4 NPT male

− G1/4 BSPP male

G 1/2B

SAE 7/16-20 UNF O-ring BOSS

ATTENTION: 

Before commissioning, the pressure transmitter must be subjected to a visual inspection.

• Fluid leakage is indicative of damage.

• Only use the pressure transmitter if it is in perfect condition concerning safety.

33

(1.3) dia.

25 (0.98)

± 0.1 dia.

1/4 in.

NPT

27

(1.06)

20

(0.79)

14

(0.55)

M12x1

29

(1.14) dia.

29 (1.14) dia.

M12 x 1

1/4 in. NPT

13 (0.51)

27

(1.06)

12

(0.47)

ca./approx.

33 (1.3)

21.3

(0.84)

13

(0.51)

27

(1.06)

29.5 (1.16) dia.

G1/4B

EN837

2

(0.08)

Wiring Diagrams

4…20 mA

(+)

(-)

1

4

2

3

4…20 mA

20

(0.79)

12

(0.47)

7/16-20 UNF

SAE J514

O-ring BOSS

G 1/2 B

EN837

3

(0.12)

G 1/2 B EN837

G 1/4 BSPP

7/16-20 UNF

Содержание 836P-N2 Series

Страница 1: ...equired for installation and commissioning Failure to comply results in personal injury or equipment damage During mounting make sure that the sealing faces at the instrument and the measuring point are clean and undamaged Safety Installation Considerations Before installation commissioning and operation be sure that the appropriate pressure transmitter has been selected in terms of measuring rang...

Страница 2: ... in Hg 100 30 in Hg 145 30inHg 200 30 in Hg 250 30 in Hg 300 Overpressure Limit 29 40 60 72 120 200 290 400 500 600 Performance Characteristics Reference Operation Conditions per IEC 61298 1 Operating Conditions Environment Load Analog signal 4 20 mA Power supply 8V 0 02 A Temperature 15 25 C 59 77 F Ambienttemperature range 1 4 in NPT 30 100 C 22 212 F G 1 4 in 30 100 C 22 212 F G 1 2 in 30 100 C...

Страница 3: ...ingCables ProcessConnection 889D F4AC 2 M12x1 connector Measuring Cell Piezoresistive measuring cell and metallic measuring diaphragm 889D R4AC 2 M12x1 right angle connector Application Measurement and monitoring of absolute and gauge pressures Process connection Thread 1 4 NPT female 1 4 NPT male G1 4 BSPP male G 1 2B SAE 7 16 20 UNF O ring BOSS ATTENTION Before commissioning the pressure transmi...

Страница 4: ...llel threads at the sealing face must be made using suitable flat gaskets and sealing rings The sealing of the tapered threads for example NPT thread is made by providing the thread with additional sealing material such as PTFE tape EN 837 2 DismountingandDisposal Dismounting Only disconnect the pressure transmitter once the system has been depressurized Disposal Incorrect disposal can put the env...

Отзывы: