Voltage Connections
With the Voltage Inputs option, the three-phase voltages can be directly
connected for voltages under 300V
L-L
, wye-wye VT connected or open-delta
VT connected. Figure 12 shows the three methods of connecting three-phase
voltages.
Figure 12 - Voltage Connections
The recommended fuse is the Bussman KTK - 1/10, 1/10 ampere Limitron® fuse,
or its equivalent.
N
L1
L2
L3
N
Wye-Wye VT Connection (Xfmr Connection = Wye)
825-P
F1
F2
F3
L1
L2
L3
L1
L2
L3
825-P
L1
L2
L3
N
Direct Connection (Xfmr Connection = Wye)
F1
F2
F3
F1, F2, and F3 are fuses.
L1
L2
L3
L1
L2
L3
Open-Delta VT Connection (Xfmr Connection = Delta)
825-P
F1
F3
Содержание 825-P
Страница 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Страница 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Страница 44: ...44 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 3 Front Panel Operation...
Страница 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Страница 104: ...104 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 6 Configuring Protection Logic Functions...
Страница 130: ...130 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 9 825 PDN DeviceNet Communication Card...
Страница 182: ...182 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 12 ASCII Serial Communications...
Страница 186: ...186 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 13 Firmware Upgrade Instructions...
Страница 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Страница 265: ......