172
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 12
ASCII Serial Communications
SET (Level 2)
The
SET
command allows you to view or change the relay settings.
When you issue the
SET
command, the relay presents a list of settings one at a
time. Enter a new setting or press Enter to accept the existing setting. Editing
keystrokes are shown in Table 102.
The relay checks each entry to ensure that it is within the setting range. If it is not,
an
Out of Range
message is generated, and the relay prompts you for the setting
again.
When all the settings are entered, the relay displays the new settings and prompts
you for approval to enable them. Type
Y
and then press Enter to enable the new
settings. The relay is disabled for as long as five seconds while it saves the new
settings. The SALARM Relay Word bit is set momentarily and the
ENABLE
LED extinguishes while the relay is disabled.
To change a specific setting, enter the command shown in Table 103.
Table 101 - Serial Port SET Commands
Command
Settings Type
Description
SET
Relay
Protection elements, timers, etc.
SET P
Port
Serial port settings for Serial Port F
SET M
Relay
I/O mapping settings
Table 102 - SET Command Editing Keystrokes
Do the Following
Results
Press Enter
Retains setting and moves to next setting.
Type ^ and then press Enter
Returns to previous setting.
Type < and then press Enter
Returns to previous setting category.
Type > and then press Enter
Moves to the next setting category.
Type END and then press Enter
Exits editing session, then prompts you to save settings.
Press Ctrl+ X
Aborts editing session without saving changes.
Table 103 - SET Command Format
SET n s TERSE
Where:
n
is left blank to enter relay settings.
n
is P to enter front serial port settings.
Содержание 825-P
Страница 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Страница 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Страница 44: ...44 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 3 Front Panel Operation...
Страница 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Страница 104: ...104 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 6 Configuring Protection Logic Functions...
Страница 130: ...130 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 9 825 PDN DeviceNet Communication Card...
Страница 182: ...182 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 12 ASCII Serial Communications...
Страница 186: ...186 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 13 Firmware Upgrade Instructions...
Страница 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Страница 265: ......