Rockwell Automation Publication 825-UM004D-EN-P - November 2012
169
ASCII Serial Communications
Chapter
12
Figure 55 - View Instantanious Meter Values Once - Example
METER T (Thermal and RTD Metering)
The
METER T
command displays the temperatures of any connected RTDs.
This command also shows the average motor current (x
I
e
), the present
% Thermal Capacity used, and the RTD % Thermal Capacity (if ambient and
winding temperatures are monitored and a winding RTD trip temperature is set).
If the motor is in overload, this command response shows the calculated time to a
thermal trip. If the motor is not in overload (e.g., see Figure 56), the time shown is
9999 seconds. The Starts Available and Time To Reset values are also displayed.
Figure 56 - Calculated Time to a Thermal Trip - Example
=>>MET
825-P Modular Date: 03/05/2003 Time: 16:44:08.404
Prot. System
L1 L2 L3
Current Magnitude (A) 21.2 21.3 21.5
Current Angle (deg) -42.0 -162.5 78.2
Average Current Magnitude (A) 21.3
Motor Load (x Ie) 0.9
GF Current-Core Balance (A) 0.00
GF Current-Core Balance Angle (deg) -76.6
GF Current-Residual (A) 0.0
GF Current-Residual Angle (deg) 72.3
Current Imbalance (%) 1.0
VAN VBN VCN VG
Voltage Magnitude L-N (V) 334 334 334 4
Voltage Angle (deg) 0.0 -119.6 120.8 -116.1
Average Phase (V) 334
Voltage Imbalance (%) 0.0
Real Power (kW) 16
Reactive Power (kVAR) 14
Apparent Power (kVA) 21
Power Factor 0.74 LAG
Frequency (Hz) 60.0
=>>
=>>MET T
825-P Modular Date: 03/05/2003 Time: 16:13:50.321
Prot. System
Max Winding RTD = 61 C
Max Bearing RTD = 48 C
Ambient RTD = 28 C
Max Other RTD = 50 C
RTD 1 WDG = 61 C
RTD 2 NONE
RTD 3 WDG = 59 C
RTD 4 WDG = 58 C
RTD 5 WDG = Open
RTD 6 WDG = 57 C
RTD 7 BRG = 48 C
RTD 8 BRG = 46 C
RTD 9 BRG = 45 C
RTD 10 BRG = 44 C
RTD 11 AMB = 28 C
RTD 12 OTH = 50 C
Motor Load (x Ie) 0.9
Thermal Capacity Used (%) 32
RTD % Thermal Capacity (%) 27
Calculated Time to Thermal Trip (sec) 9999
Time to Reset (min) 0
=>>
Содержание 825-P
Страница 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Страница 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Страница 44: ...44 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 3 Front Panel Operation...
Страница 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Страница 104: ...104 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 6 Configuring Protection Logic Functions...
Страница 130: ...130 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 9 825 PDN DeviceNet Communication Card...
Страница 182: ...182 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 12 ASCII Serial Communications...
Страница 186: ...186 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 13 Firmware Upgrade Instructions...
Страница 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Страница 265: ......