Digital Module Operation in a Control System
Chapter 1
To help prevent other owner-controllers from receiving potentially erroneous
data, use the following steps when changing the configuration of a module in a
multiple owner scenario while online.
1. For each owner-controller, inhibit the connection to the module either
in the software on the Connection tab or the message dialog box
warning you of the multiple owner condition.
2. Make the appropriate configuration data changes in the software.
For more information on how to use the Logix Designer application to
change the configuration, see the following:
– Standard modules - Chapter 6,
Configure a Standard Module on
– Safety modules - Chapter 7,
Configure and Replace Safety Modules
3. Repeat
for all owner-controllers, to make the exact
same changes in each.
4. Clear the Inhibit checkbox in each owner-controller configuration.
Construct a System
Before you use your Compact 5000 I/O digital modules, you must complete
tasks that are based on the way that you use the modules. That is, if the
modules are used locally, remotely or both locally and remotely.
Local I/O Modules
Complete the following:
1. Install a CompactLogix 5380, CompactLogix 5480, or
Compact GuardLogix 5380 controller.
2. Install the modules to the right of the controller.
3. Install the end cap on the last module in the local system.
5069-OBV8S
SIL2 CPU
5069-L3100ERMS2
Compact GuardLogix
5069-OBV8S
5069-IB8S
5069-IB8S
OUTPUT
OUTPUT
SA P
ow
er
MOD P
ow
er
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
SA P
ow
er
MOD P
ow
er
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
Standard Modules
Safety Modules
™
NET B1
LINK B1
NET A1
LINK A1
NET A2
LINK A2
SPEED X1
LINK X1
OK
RUN
FORCE
FAN 1
SD
FAN 2
Compact
Logix
5480
B1
A1
1
2
A2
5069-L46ERMW
CONTROLLER
UPS
MP
SA
R
B
F
R
B
F
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
IMPORTANT
Remember, you must use a Compact GuardLogix 5380 controller if
the local Compact 5000 I/O digital modules includes safety
modules.
For more information on controller compatibility, see
Software Compatibility on page 18
.
IMPORTANT
The end cap in a CompactLogix 5380, CompactLogix 5480, or
Compact GuardLogix 5380 control system covers the exposed
interconnection on the last module on the DIN rail.
If you do not install an end cap on the last module on the DIN rail,
equipment damage or injury can occur.
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......