Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
235
Module Tag Definitions
Appendix B
5069-IB16 Module Tags
This section describes the tags that are associated with the 5069-IB16 module.
You use the 5069-IB16 module profile in your Logix Designer application
project with the 5069-IB16K module.
Configuration Tags
Table 61
describes the 5069-IB16 module configuration tags.
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
SA P
ow
er
MOD P
ow
er
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
Standard Modules
Table 61 - 5069-IB16 Module Configuration Tags
Name
Data Type
Definition
Valid Values
Counterxx.InputOffOnFilter
SINT
The amount of time that a signal must be in the on state
before the input data indicates the on state.
The amount of time is indicated using an enumeration.
Not all products support all enumeration values.
• 9 = 0 μs
• 10 = 100 μs
• 11 = 200 μs
• 12 = 500 μs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
Counterxx.InputOnOffFilter
SINT
The amount of time that a signal must be in the off state
before the input data indicates the off state.
The amount of time is indicated using an enumeration.
Not all products support all enumeration values.
• 9 = 0 μs
• 10 = 100 μs
• 11 = 200 μs
• 12 = 500 μs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
Counterxx.RolloverAtPreset
BOOL
Determines whether the simple counter rolls over to 0
when it reaches O:Preset (1) or at 2147483647 (0).
• 0 = Maximum value
• 1 = Preset value
Ptxx.InputOffOnFilter
SINT
The amount of time that a signal must be in the on state
before the input data indicates the on state.
The amount of time is indicated using an enumeration.
Not all products support all enumeration values.
• 9 = 0 μs
• 10 = 100 μs
• 11 = 200 μs
• 12 = 500 μs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
Ptxx.InputOnOffFilter
SINT
The amount of time that a signal must be in the off state
before the input data indicates the off state.
The amount of time is indicated using an enumeration.
Not all products support all enumeration values.
• 9 = 0 μs
• 10 = 100 μs
• 11 = 200 μs
• 12 = 500 μs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......