Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Chapter 7
Configure and Replace Safety Modules
Reset to Out-of-Box Configuration
When the Logix Designer application is online, the Safety tab of the Module
Properties dialog box displays the current configuration ownership. When the
opened project owns the configuration, Local is displayed.
When a second device owns the configuration, Remote is displayed, along with
the SNN, and node address or slot number of the configuration owner.
Communication error is displayed if the module read fails.
If the connection is Local, you must inhibit the module connection before you
reset ownership. To inhibit the module:
1. Right-click the module and choose Properties.
2. On the Connection tab, click Inhibit module.
3. Click Apply and then OK.
Complete the following steps to reset the module to its out-of-box
configuration when online.
1. Right-click the module and choose Properties.
2. On the Safety tab, click Reset Ownership.
3. When a dialog box appears asking if you want to continue with the reset,
read it and click Yes.
Содержание 5069-IA16
Страница 16: ...16 Rockwell Automation Publication 5069 UM004A EN P April 2019 Preface Notes ...
Страница 106: ...106 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 3 Input Module Features Notes ...
Страница 190: ...190 Rockwell Automation Publication 5069 UM004A EN P April 2019 Chapter 6 Configure a Standard Module Notes ...
Страница 230: ...230 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix A TroubleshootYour Module Notes ...
Страница 272: ...272 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix B ModuleTag Definitions Notes ...
Страница 290: ...290 Rockwell Automation Publication 5069 UM004A EN P April 2019 Appendix D Safety Data for Safety Modules Notes ...
Страница 294: ...294 Rockwell Automation Publication 5069 UM004A EN P April 2019 Index Notes ...
Страница 295: ......