164
Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017
Chapter 8
Troubleshooting
Terminal Does Not Start
Properly
This section provides general troubleshooting information to assist you when
trying to isolate anomalies.
Check for Adequate Power
A terminal that does not receive adequate power could result in unpredictable
behavior. Refer to
for power requirements.
Check Indicators at Startup
When the terminal starts, the fault and comm indicators flash on and off, then
the comm indicator flashes to signal progress during startup. When startup is
complete, the comm indicator remains on, and is controlled by the
communication driver or application. The comm indicator typically flashes when
communication is active.
If the indicators remain off, the power supply or logic module has failed. Check
the power cable:
•
If the power is not within range, replace the power supply.
•
If the power is within range, replace the logic module or terminal.
The table shows indicator states if the terminal powers on and stops during
startup.
Table 78 - Indicator States if Terminal Stops during Startup
Fault (Red)
Indicator
Comm (Green)
Indicator
Description
Blinking
Off
Recoverable firmware error. Last firmware download failed.
Reload the firmware by using the Firmware Upgrade Wizard (FUW).
On
Off
Non-recoverable hardware fault with logic module:
•
For 400 and 600 terminals, replace the terminal.
•
For 700 to 1500 terminals, replace the logic module.
Blinking
Non-recoverable hardware fault with display module:
•
For 400 and 600 terminals, replace the terminal.
•
For 700 to 1500 terminals, replace the display module.
Содержание 2711P-B10C4A8
Страница 4: ...4 Rockwell Automation Publication 2711P UM006E EN P January 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 2711P UM006E EN P January 2017 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 2711P UM006E EN P January 2017 Preface Notes...
Страница 118: ...118 Rockwell Automation Publication 2711P UM006E EN P January 2017 Chapter 4 Windows CE Operating System Notes...
Страница 138: ...138 Rockwell Automation Publication 2711P UM006E EN P January 2017 Chapter 5 Install and Replace Components Notes...
Страница 176: ...176 Rockwell Automation Publication 2711P UM006E EN P January 2017 Chapter 8 Troubleshooting Notes...
Страница 186: ...186 Rockwell Automation Publication 2711P UM006E EN P January 2017 Index Notes...
Страница 187: ......