Publication 2707-UM005B-EN-P - July 2000
Installing the MicroView Operator Interface
6-5
Connecting DC Power
During run-time operation, the MicroView is supplied with 24 VDC
power by the MicroLogix controller through the cable connected to
the Communication Port.
When the MicroView is connected to a personal computer for
application uploading/downloading a separate DC power source must
be connected to the Power Port. The MicroView accepts power
supply voltages from 11 to 25 VDC. The DC power supply must be
capable of providing at least 1.5 watts.
The following MicroView accessories meet these requirements. Use
either depending upon your source voltage.
• 120 VAC Input, use AC to DC Adapter (Catalog No. 2707-PS120)
• 220 VAC Input, use AC to DC Adapter (Catalog No. 2707-PS220)
To connect the communications cabling, between the MicroView and
MicroLogix, refer to Chapter 7.