Frame A Field Controller Part Replacement Procedures
Chapter 3
Table 9 - DIP Switch S3 and S4 Settings - FIR1-
xx
-FC
2. Install the isolation sheet (if present) before installing the pulse
transformer and switching power supply boards.
3. Install the configured pulse transformer board and switching power
supply board in reverse order of removal.
IMPORTANT
A blank cell below a switch in
indicates that the setting is “OFF”.
Device Output
Current (Amps)
DIP Switch S3
DIP Switch S4
S3-1
S3-2
S3-3
S3-4
S3-5
S3-6
S3-7
S3-8
S4-1
S4-2
S4-3
S4-4
S4-5
S4-6
S4-7
S4-8
17
ON
ON
60
ON
ON
ON
ON
ON
ON
120
ON
ON
ON
ON
ON
ON
ATTENTION:
Failure to install the Isolation sheet below the pulse transformer
and switching power supply boards can result in damage to the field
controller.
ATTENTION:
Each gate lead cable must be connected to the exact connector
from which it was removed on the pulse transformer circuit board or damage
to the device can occur. See
for gate lead pinouts.