40
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 1
Installation/Wiring
General Notes
All Drive Frames
• The motor cable should be kept as short as possible in order to avoid
electromagnetic emission as well as capacitive currents.
• Use of line filters in ungrounded systems is not recommended.
• Conformity of the drive with CE EMC requirements does not
guarantee an entire machine installation complies with CE EMC
requirements. Many factors can influence total machine/installation
compliance.
Frame C Drives Only
• If the plastic top panel is removed or the optional conduit box is not
installed, the drive must be installed in an enclosure with side openings
less than 12.5 mm (0.5 in.) and top openings less than 1.0 mm (0.04 in.)
to maintain compliance with the LV Directive.
Essential Requirements for CE Compliance
Conditions 1...4 listed below
must be
satisfied for PowerFlex drives to meet
the requirements of
EN61800-3
.
. Refer to
for additional
grounding recommendations.
2. Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
3. All shielded cables should terminate with the proper shield connector.
.
Table 12 - PowerFlex 400 – EN61800-3 Compliance
PowerFlex 400 Drive First Environment Restricted
First Environment Unrestricted
kW
(HP)
Cat No.
22C-...
Required Filter
(Allen-Bradley)
Restrict
Motor
Cable to
(Meters)
Install
Drive and
Filter in
Shielded
Enclosure
Required Filter
Restrict
Motor
Cable to
(Meters)
Install
Drive and
Filter in
Shielded
Enclosure
200...240 Volts
2.2 (3.0)
B012N103
22-RF034-CS
10
No
22-RF034-CS
1
Required
3.7 (5.0)
B017N103
22-RF034-CS
10
No
22-RF034-CS
1
Required
5.5 (7.5)
B024N103
22-RF034-CS
10
No
22-RF034-CS
1
Required
7.5 (10)
B033N103
22-RF034-CS
10
No
22-RF034-CS
1
Required
11 (15)
B049A103
22-RFD070
150
Required
Deltron MIF Series 50
Required
15 (20)
B065A103
22-RFD100
150
Required
Deltron MIF Series 50
Required
18.5 (25)
B075A103
22-RFD100
150
Required
Deltron MIF Series 50
Required
22 (30)
B090A103
22-RFD150
150
Required
Deltron MIF Series 50
Required
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...