background image

Rockwell Automation Publication 1784-IN047B-EN-P - February 2018

5

USB-to-ControlNet Cable

Status Indicators

Specifications

Indicator

Status

Description

USB

Green

The cable is configured, but no network traffic is 
present.

Flashing green

Network traffic is present.

Off

Unable to transfer data.
• Disconnected from host.
• In one of the following states:

– default
– powered
– address
– suspend

Module Status (MS)

Green

The cable is operating normally.

Off

No power to the cable.

Flashing green

The cable is operating in a normal condition and 
is online with no connections established.
• The cable may be in Standby mode.
• The cable needs commissioning due to 

missing, incomplete, or incorrect 
configuration.

Flashing red

The cable has a recoverable fault.

Red

The cable has an unrecoverable fault and may 
need to be replaced.

Flashing red/green

The cable is performing a self-test.

ControlNet Network 
Status (NS)

Off

Not on network.

Red

Network interface faulted.

Flashing red/green

Invalid network configuration (for example, a 
MAC ID above UMAX).

Flashing red

• Duplicate node detected.
• Link  fault.
• No  MAC  frames  received.

Flashing green

• Temporary channel error.
• Listen  only.

Green

Normal operation. MAC frame received without 
error.

USB

ControlNet 
Network Status

Module 
Status

Attribute

1784-U2CN

Enclosure type rating

Meets IP30

Supply voltage

5.25V DC

Supply current

225 mA

Isolation voltage

30V continuous, Basic Insulation Type

 

Type tested at 500V AC for 60 s, ControlNet to USB

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation 
Wiring and Grounding Guidelines, publication 

1770-4.1

.

2 - on communication ports

ControlNet current value

70 mA @ 24V

Temperature, operating 
IEC 60068-2-1 (Test Ad, Operating Cold),

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F)

Temperature, nonoperating
IEC 60068-2-1 

 

(Test Ab, Unpackaged Nonoperating Cold),

 

IEC 60068-2-2 

 

(Test Bb, Unpackaged Nonoperating Dry Heat),

 

IEC 60068-2-14 

 

(Test Na, Unpackaged Nonoperating Thermal Shock):

-10…+85 °C (14…185 °F)

Temperature, ambient, max.

55 °C (131 °F)

Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Emissions
CISPR 11

Group 1, Class A

ESD immunity
IEC 61000-4-2

8 kV air discharges

Radiated RF immunity
IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM 

 

from 80…2000 MHz

 

10V/m with 200 Hz 50% Pulse 100% AM 

 

at 900 MHz

 

10V/m with 200 Hz 50% Pulse 100% AM 

 

at 1890 MHz

 

10V/m with 1 kHz sine-wave 80% AM 

 

from 2000…2700 MHz

Certifications

Certifications

 

(when product is marked)

(1)

(1)

See the Product Certification link at

 

http://www.ab.com

 for Declarations of Conformity, Certificates, and 

other certification details.

1784-U2CN

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. 
See UL File E65584.

CE

European Union 2004/108/EC EMC Directive, compliant with:

 

EN 61326-1; Meas./Control/Lab., Industrial Requirements

 

EN 61000-6-2; Industrial Immunity

 

EN 61000-6-4; Industrial Emissions

 

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

EN 61000-6-4; Industrial Emissions

KCC

Article 58-2 of Radio Waves Act, Clause 3

CI

ControlNet International conformance tested to ControlNet specifications

Содержание 1784-U2CN

Страница 1: ...etwork by using an unused USB port on the computer The product replaces the 1784 PCC communication card for computers that do not have PCMCIA slots Topic Page Summary of Changes 1 About the Cable 1 Pr...

Страница 2: ...lla sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio oltr...

Страница 3: ...lass non dangereux avant de changer les piles Environment and Enclosure ATTENTION This equipment is intended for use in overvoltage Category II applications as defined in EN IEC 60664 1 at altitudes u...

Страница 4: ...r traffic analyzer software For more information on Frontline s product go to either http www rockwellautomation com encompass or http www fte com ATTENTION Thisequipmentissensitivetoelectrostaticdisc...

Страница 5: ...Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 2 on communication ports ControlNet current value 70 mA 24V Tem...

Страница 6: ...contact your local Allen Bradley distributor or Rockwell Automation sales representative Resource Description ControlNet Coax Media Planning and Installation Guide publicationCNET IN002 Provides Contr...

Страница 7: ...Rockwell Automation Publication 1784 IN047B EN P February 2018 7 USB to ControlNet Cable Notes...

Страница 8: ...umentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra d...

Отзывы: