Use I/O Modules with CompactLogix 5370 L2 Controllers
Chapter 8
Channel Input Type and Filter Frequency Selection Update Time
When you enable an embedded analog input channel, you must select an input
type and a filter frequency for that input. The selections that are made determine
the value that is required when calculating channel update time.
shows the channel update times for each channel input type and filter
frequency selection.
Cold Junction Compensation Update Times
When you use any of the thermocouple input types on your embedded analog
input, you must account for more voltage at the junction of the thermocouple
field wires and the input point. More voltage can alter the input signal on that
point and, therefore, affect the update time of that channel.
The process to account for increased voltage at an input point by using a
thermocouple type input is cold junction compensation (CJC). You enable CJC
for a given channel on the Input Configuration tab of the Module Configuration
dialog box, as shown in the following graphic.
IMPORTANT
Each channel input type has multiple ranges or types. For example, a voltage
input type can use one of six voltage ranges, as listed in
Table 10 on page 187
.
Regardless of which voltage range the channel uses, the channel update time
remains the same. For more information, see
.
Table 12 - Channel Update Times
Filter Frequency
Selection
(1)
(1) Filter frequency selections are made on the Input Configuration tab of the Module Properties dialog box.
Channel Update Times Based on Input Type Selection
Voltage, Current or
Thermocouple Input Type
Resistance or RTD Input
Type
10 Hz
307 ms
614 ms
50 Hz
67 ms
134 ms
60 Hz
57 ms
114 ms
250 Hz
19 ms
38 ms
500 Hz
13 ms
26 ms
1 kHz
11 ms
22 ms