Protocol Configuration
Modbus Slave Memory Map
The modbus Memory map is summarized in and detailed in :
Modbus to MicroLogix Memory Map - Summary
Modbus
Addressing
Description
Valid MicroLogix Addressing
File Type
Data File Number Address
0001 to 4096
Read/Write Modbus Coil Data space
Bit (B) or Integer (N)
3 to 255
bits 0 to 4095
10001 to 14096
Read-Only Modbus Contact Data space
Bit (B) or Integer (N)
3 to 255
bits 0 to 4095
30001 to 30256
Read-Only Modbus Input Register space
Bit (B) or Integer (N)
3 to 255
words 0 to 255
30501 to 30532
Modbus Communication Parameters
Communication Status File
-
-
31501 to 31566
Read-Only System Status File space
Status (S)
2
words 0 to 65
40001 to 40256
Read/Write Modbus Holding Register space Bit (B) or Integer (N)
3 to 255
words 0 to 255
40257 to 41280
(1)
Read/Write Modbus Holding Register space Bit (B) or Integer (N)
3 to 255
words 0 to 255 of
four Holding
Register files
41501 to 41566
Read/Write System Status File space
Status (S)
2
words 0 to 65
41793 to 42048
Read/Write Modbus Holding Register space Bit (B) or Integer (N)
3 to 255
words 0 to 255 of
the last Holding
Register file
(1) These addresses only become active when specially configured for expanded holding registers.