4

     DC-Input/Relay-Output Combination Module

Publication 1762-IN018B-EN-P - July 2013

North American Hazardous Location Approval

The following modules are North American Hazardous Location approved: 1762-IQ8OW6

The following information applies when 
operating this equipment in hazardous 
locations:

Informations sur l’utilisation de cet 
équipement en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are 
suitable for use in Class I Division 2 Groups A, B, C, 
D, Hazardous Locations and nonhazardous 
locations only. Each product is supplied with 
markings on the rating nameplate indicating the 
hazardous location temperature code. When 
combining products within a system, the most 
adverse temperature code (lowest "T" number) may 
be used to help determine the overall temperature 
code of the system. Combinations of equipment in 
your system are subject to investigation by the 
local Authority Having Jurisdiction at the time of 
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu'à une utilisation en environnements de 
Classe I Division 2 Groupes A, B, C, D dangereux et non 
dangereux. Chaque produit est livré avec des 
marquages sur sa plaque d'identification qui indiquent 
le code de température pour les environnements 
dangereux. Lorsque plusieurs produits sont combinés 
dans un système, le code de température le plus 
défavorable (code de température le plus faible) peut 
être utilisé pour déterminer le code de température 
global du système. Les combinaisons d'équipements 
dans le système sont sujettes à inspection par les 
autorités locales qualifiées au moment de l'installation.

WARNING

EXPLOSION HAZARD

Do not disconnect equipment 
unless power has been removed 
or the area is known to be 
nonhazardous.

Do not disconnect connections to 
this equipment unless power has 
been removed or the area is 
known to be nonhazardous. 
Secure any external connections 
that mate to this equipment by 
using screws, sliding latches, 
threaded connectors, or other 
means provided with this product.

Substitution of components may 
impair suitability for Class I, 
Division 2.

If this product contains batteries, 
they must only be changed in an 
area known to be nonhazardous.

All wiring must comply with 
N.E.C. article 501-4(b).

The interior of the enclosure must 
be accessible only by the use of a 
tool.

For applicable equipment (relay 
modules, etc.), exposure to some 
chemicals may degrade the 
sealing properties of materials 
used in the following devices: 
Relays, Epoxy. It is recommended 
that the User periodically inspect 
these devices for any degradation 
of properties and replace the 
module if degradation is found.

AVERTISSEMENT

RISQUE D’EXPLOSION

Couper le courant ou s’assurer que 
l’environnement est classé non 
dangereux avant de débrancher 
l'équipement.

Couper le courant ou s'assurer que 
l'environnement est classé non 
dangereux avant de débrancher les 
connecteurs. Fixer tous les 
connecteurs externes reliés à cet 
équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou 
autres moyens fournis avec ce 
produit.

La substitution de composants peut 
rendre cet équipement inadapté à une 
utilisation en environnement de 
Classe I, Division 2.

S’assurer que l’environnement est 
classé non dangereux avant de 
changer les piles.

Содержание 1762-IQ8OW6

Страница 1: ...an Hazardous Location Approval 4 Module Description 5 Install the DC Input Relay Output Combination Module 6 Mount the Module on a DIN Rail 6 Mount the Module on a Panel 7 Wire the DC Input Relay Output Combination Module 8 Ground the DC Input Relay Output Combination Module 9 Wire the Finger safe Terminal Block 9 System Assembly 10 Input Memory Map 11 Output Memory Map 12 Specifications 13 Additi...

Страница 2: ...tion Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibite...

Страница 3: ...nternational Electrotechnical Commission IEC designations ATTENTION Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins Follow these guidelines when you handle the module Touch a grounded object to discharge static potential Wear an approved wrist strap grounding device Do not touch the bus connector or connector pins Do not touch circuit compon...

Страница 4: ...nt sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using ...

Страница 5: ...em Description 1a upper panel mounting tab 5 bus connector cover 1b lower panel mounting tab 6 flat ribbon cable with bus connector female pins 2 I O diagnostic LEDs 7 terminal block 3 module door with terminal identification label 8 DIN rail latch 4 bus connector with male pins 9 pull loop 1a 7 6 1b 4 5 3 9 1a 6 8 1b 2 ...

Страница 6: ...mentarily open and lock into place Use DIN rail end anchors Allen Bradley part number 1492 EA35 or 1492 EAH35 for vibration or shock environments ATTENTION Do not remove protective debris strip until after the module and all other equipment near the module is mounted and wiring is complete Once wiring is complete and the module is free of debris carefully remove protective debris strip Failure to ...

Страница 7: ... a good ground contact Mounting screws are required on every module TIP For environments with greater vibration and shock concerns use the panel mounting method described below instead of DIN rail mounting End Anchor End Anchor MicroLogix 1200 Controller MicroLogix 1200 Expansion I O MicroLogix 1200 Expansion I O MicroLogix 1200 Expansion I O 90 3 54 100 3 94 40 4 1 59 40 4 1 59 14 5 0 57 For more...

Страница 8: ...field power supply are sinking field devices Field devices connected to the positive side V of the field supply are sourcing field devices 2 Surge Suppression Connecting surge suppressors across your external inductive load will extend the life of the relay contacts For additional details refer to Industrial Automation Wiring and Grounding Guidelines Allen Bradley publication 1770 4 1 ATTENTION Be...

Страница 9: ...ial Automation Wiring and Grounding Guidelines Allen Bradley publication 1770 4 1 for additional information Wire the Finger safe Terminal Block When wiring the terminal block keep the finger safe cover in place 1 Route the wire under the terminal pressure plate You can use the stripped end of the wire or a spade lug The terminals will accept a 6 35 mm 0 25 in spade lug 2 Tighten the terminal scre...

Страница 10: ...ed to remove the finger safe cover insert a screw driver into one of the square wiring holes and gently pry the cover off If you wire the terminal block with the finger safe cover removed you will not be able to put it back on the terminal block because the wires will be in the way Wire Type Wire Size Terminal Screw Torque Solid Cu 90 C 194 F 0 325 2 080 mm2 22 14 AWG 0 90 Nm 8 lb in Stranded Cu 9...

Страница 11: ...r expansion I O begins with slot 1 ATTENTION EXPLOSION HAZARD In Class I Division 2 applications the bus connector must be fully seated and the bus connector cover must be snapped in place In Class I Division 2 applications all modules must be mounted in direct contact with each other as shown on page 6 If DIN rail mounting is used an end stop must be installed ahead of the controller and after th...

Страница 12: ...e only w user can write but outputs not available 0 always at 0 or OFF state The output addressing scheme for 1762 expansion I O is shown below 1 I O located on the controller embedded I O is slot 0 I O added to the controller expansion I O begins with slot 1 Word Bit Position 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 0 w w w w w w w w O0 x 0 0 Output Data File Slot Number 1 Word Alway...

Страница 13: ...ts are driven by a current sourcing field device Field devices connected to the negative side DC Common of the field power supply are sinking field devices Field devices connected to the positive side V of the field supply are sourcing field devices Operating Voltage Range 10 30V DC 30 C 86 F 10 26 4V DC 65 C 149 F Number of Inputs 8 On state Voltage Min 10V DC Off state Voltage Max 5V DC On state...

Страница 14: ...tinuous Amps per Point Max Amperes 1 1 Surge Suppression Connecting surge suppressors across your external inductive load will extend the life of the relay contacts For additional details refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Voltamperes Make Break Make Break 240V AC 2 5 A 7 5 A 0 75 A 1800VA 180VA 120V AC 15 A 1 5 A 125V DC 1 0 A 0 22 A 2 2 For DC vol...

Страница 15: ... Operation 1 5 g Shock Operating 30 g panel mounted 3 pulses per axis Relay Operation 7 g Non Operating 50 g panel mounted 3 pulses per axis 40 g DIN Rail mounted Vender ID Code 1 Product Type Code 7 Product Code 98 Hazardous Environment Class Class I Division 2 Hazardous Location Groups A B C D ISA ANSI 12 12 01 C UL under CSA C22 2 No 213 Radiated and Conducted Emissions EN50081 2 Class A ESD Im...

Страница 16: ... us UL Listed Industrial Control Equipment certified for US and Canada UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers...

Страница 17: ...nstalling wiring and operating a MicroLogix 1200 programmable controller system MicroLogix 1200 Programmable Controllers Installation Instructions publication 1762 IN006 Installation guide for the MicroLogix 1200 programmable controller MicroLogix 1100 Programmable Controllers User Manual publication 1763 UM001 A more detailed description of how to install and use your MicroLogix 1100 programmable...

Страница 18: ...18 DC Input Relay Output Combination Module Publication 1762 IN018B EN P July 2013 Notes ...

Страница 19: ...DC Input Relay Output Combination Module 19 Publication 1762 IN018B EN P July 2013 Notes ...

Страница 20: ...perational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature United S...

Отзывы: