Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
163
Develop Applications
Chapter 10
Determine if I/O Communication has Timed Out
This example can be used with the 1756-L7
x
or 1756-L6
x
controllers:
•
The GSV instruction gets the status of the I/O status indicator (via the
LEDStatus attribute of the Module object) and stores it in the
IO_LED tag.
•
IO_LED is a DINT tag that stores the status of the I/O status indicator or
status display on the front of the controller.
•
If IO_LED equals 2, then at least one I/O connection has been lost and
the Fault_Alert is set.
Figure 40 - GSV Used to Identify I/O Timeout
For more information about attributes available with the Module object, see the
Logix5000 Controllers General Instructions Reference Manual, publication
Determine if I/O Communication to a Specific I/O Module has
Timed Out
If communication times out with a device (module) in the I/O configuration of
the controller, the controller produces a fault code and fault information for the
module. You can use GSV instructions to get fault code and information via the
FaultCode and FaultInfo attributes of the Module object.
For more information about attributes available with the Module object, see the
Logix5000 Controllers General Instructions Reference Manual, publication
Содержание 1756-L63XT
Страница 4: ...4 Rockwell Automation Publication 1756 UM001O EN P October 2014 Summary of Changes Notes...
Страница 18: ...18 Rockwell Automation Publication 1756 UM001O EN P October 2014 Preface Notes...
Страница 78: ...78 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 3 Start Using the Controller Notes...
Страница 126: ...126 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 7 Manage Controller Communication Notes...
Страница 136: ...136 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 8 I O Modules...
Страница 168: ...168 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 10 Develop Applications Notes...
Страница 182: ...182 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 12 Redundant Systems Notes...
Страница 210: ...210 Rockwell Automation Publication 1756 UM001O EN P October 2014 Index Notes...
Страница 211: ......