Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
47
ControlLogix I/O Modules
Chapter 5
The control, diagnostics, and alarming functions must be performed in sequence.
For more information on faults, see
.
You can also wire two isolated, standard outputs in series to critical actuators. In
the event that a failure is detected, the outputs from each of the output modules
must be set to OFF to make sure the field devices de-energize.
shows
how to wire two isolated, standard outputs in series to critical actuators.
Figure 20 - ControlLogix Standard Output Module Wiring with Two Modules
Using Analog Input Modules
There are a number of general application considerations that you must make
when using analog input modules in a SIL 2 application. The following section
describes those considerations specific to the use of analog input modules.
To achieve SIL 2, two analog input modules are required. Field sensors must be
wired to channels on each module and compared within a deadband. Whether
one or two field sensors are required is dependent on the Probability of Failure on
Demand (PFD) value of the sensor.
Conduct Proof Tests
Periodically perform a system validation test. Manually or automatically test all
inputs to make sure that they are operational. Field signal levels should be varied
over the full operating range to make sure that the corresponding channel data
varies accordingly. For more information, see
.
Wire output point to
input point to verify
the correct state of the
output.
Input
Standard Isolated
Output Module #2
43364
Standard Isolated
Input Module
V-/L2
V+/L1
Output
Standard Isolated
Output Module #1
V+/L1
Output
Actuator
V-/L2
V+/L1
Содержание 1756-L6 Series
Страница 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Страница 60: ...60 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 5 ControlLogix I O Modules Notes ...
Страница 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Страница 120: ...120 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix C PFD Calculations for a SIL 2 System Notes ...
Страница 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Страница 133: ...Allen Bradley Motors ...