50
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 3 Configurable Flowmeter Module Features and Operational Modes
•
If the input frequency is greater than 300Hz, the K-factor used
is always 100.0. There is no K-factor calculation over 100Hz.
To use Gross Rate, you must set the K-factor values in Module Tags, as shown.
Net Rate
Use Net Rate to convert Net Volume to a rate by using this equation:
Fill Total Target
Fill Total Target is the user-defined final volume (in engineering units) for a
total fill.
Name
Style
Data type
Value
Change during operation
C.Operations[0].kFactStruct.kFactorForChan[0]
Float
REAL
25.0
1
Yes
C.Operations[0].kFactStruct.kFactorForChan[1]
Float
REAL
25.0
1
Yes
C.Operations[0].kFactStruct.kFactorForChan[2]
Float
REAL
71.0
Yes
C.Operations[0].kFactStruct.kFactorForChan[3]
Float
REAL
111.0
Yes
C.Operations[0].kFactStruct.kFactorForChan[4]-
C.Operations[0].kFactStruct.kFactorForChan[12]
Float
REAL
0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[0]
Float
REAL
0.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[1]
Float
REAL
100.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[2]
Float
REAL
200.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[3]
Float
REAL
300.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[4]-
C.Operations[0].kFactStruct.FreqAtKFactor[12]
Float
REAL
0
Yes
1
To avoid discontinuity when interpolating Gross Rate, make sure the values in C.Operations[0].kFactStruct.kFactorForChan[0] and
C.Operations[0].kFactStruct.kFactorForChan[1] match.
IMPORTANT
For more information on setting values in the Module Tags, see
Configure the Configurable Flowmeter Module on page 69
Net Rate =
Total Counts in Meter Sample
Sample Interval
K-factor
x
Meter Factor
x CCF
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...