Interpret Status Indicators
Refer to the following diagram and table for information on how to interpret the
status indicators.
Indicator Status for Module
Indicator
State
Description
Module
status
Off
No power applied to device.
Green
Device operating normally.
Flashing green
Device needs commissioning due to missing, incomplete, or
incorrect configuration.
Flashing red
Recoverable fault.
Red
Unrecoverable fault may require device replacement.
Flashing red/green
Device is in self-test mode.
Network
status
Off
Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Flashing green
Device is online but has no connections in the established state.
Green
Device is online and has connections in the established state.
Flashing red
One or more I/O connections are in timed-out state.
Red
Critical link failure – failed communication device. Device detected
error that prevents it from communicating on the network.
Flashing red/green
Communication faulted device – the device has detected a network
access error and is in communication faulted state. Device has
received and accepted an Identity Communication Faulted Request
– long protocol message.
Channel
status
Off
Module in CAL mode.
Solid green
Channel actively controlling outputs
Flashing green
Channel calibrating
Flashing red
Open wire or no field power present
Solid red
Unused
Module status
Network status
Status of output 0
Status of output 1
Status of output 2
Status of output 3
44352
4-20mA
Analog
Output
Module
Status
Network
Status
1734
OE4C
0
1
2
3
NODE: