Auto-addressing with a
1734-PDN Adapter and
POINT Guard I/O Modules
Sequential auto-addressing is where the leftmost node address is configured and a
parameter is set in that module that automatically addresses nodes to the right of
the module. The leftmost node can be a POINT Guard I/O module or a
standard POINT I/O module.
Follow these steps to use the auto-address feature.
1.
Reset any modules that you are not sure are out-of-box.
2.
Attach the first module to the 1734-PDN adapter.
3.
Use the node commissioning tool to set the node address of this module.
4.
Attach the additional nodes to the right of the module used in
steps
and
5.
Perform the auto-address feature on the module used in steps
and
A. Set the address of the leftmost I/O module.
B. When you configure the leftmost module, set Sequential
AutoAddress to ‘Sequential Address’.
The module sequences the rest
of the modules to its right in
the group.
Содержание 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S Installation User Manual...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013C EN P August 2010 Summary of Changes Notes...
Страница 38: ...38 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 2 Safety Functions Notes...
Страница 52: ...52 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 3 Install the Module Notes...
Страница 58: ...58 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 4 Wire the Module Notes...
Страница 64: ...64 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 5 Power Supply Examples Notes...
Страница 144: ...144 Rockwell Automation Publication 1734 UM013C EN P August 2010 Appendix D Specifications Notes...
Страница 153: ......
Страница 154: ......
Страница 155: ......