POINT I/O Dual Port EtherNet/IP Adapter
Publication 1734-IN041F-EN-P - May 2019
Install the Adapter
Follow this procedure to install the adapter on the DIN rail.
1.
Position the adapter module vertically above an IEC standard (35 x 7.5 x 1 mm)
top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number
199-DR1
;
46277-3
;
EN50022
). Make sure that the DIN rail lock is in a
horizontal position.
ATTENTION:
This product is grounded through the DIN rail to chassis ground.
Use zinc plated chromate-passivated steel DIN rail to assure proper grounding.
The use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail
properly. Refer to Industrial Automation Wiring and Grounding Guidelines,
Rockwell Automation publication
, for more information.