All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
8
Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
3AC 400V
*)
3AC 480V
*)
Hold-up Time
typ.
50ms
50ms
at 48V, 10A, see Fig. 7-1
min.
40ms
40ms
at
48V,
10A,
see
Fig.
7-1
typ.
25ms
25ms
at
48V,
20A,
see
Fig.
7-1
min.
20ms
20ms
at 48V, 20A, see Fig. 7-1
*)
Curves and figures for operation on only two legs of a 3-phase system can be found in section 25.4.
Fig. 7-1
Hold-up time vs. input voltage
Fig. 7-2
Shut-down behavior, definitions
0
10
20
30
40
50ms
320
360
400
440
3x480Vac
Input Voltage
Hold-up Time
48V, 10A, typ.
48V, 20A, typ.
48V, 10A, min.
48V, 20A, min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage