Rockwell Automation Publication 1606-RM105A-EN-P - July 2020
11
Operating Diagrams
Active Signal
The signal “Active” (pin 7) is an opto-coupler output, which is low ohmic while
buffer capacitors, are discharged.
, and
.
Ready Signal
The signal “Ready” (pin 8) is an opto-coupler output, which is low ohmic when
buffer capacitors, are fully charged.
, and
.
Figure 8 - Operating Diagram
Figure 9 - Signal Schematic
Ready
t
Active
t
Optocoupler high ohmic
Optocoupler high ohmic
Optocoupler low ohmic
Optocoupler
low ohmic
V
Mains
t
V
Buffer
Capacitor
t
V
out
t
Charging Mode
LED
t
Buffer Mode
Hold-up Time Power Supply
Standby
Mode
10 Hz
1.25 Hz
8 Ready
7 Active
6 +
5,1V
3 mA
9 Inhibit
Buffer
Module
Attributes
Values
Notes
Signal voltage
Max
35V DC
Voltage between pin 6 and 7
Signal current
Max
10 mA
Voltage drop across opto-coupler
—
0.9V / 3V
At 1 mA / 5 mA while opto-coupler is low ohmic
Leakage current
Max
50 μA
While opto-coupler is high ohmic
Isolation voltage
Dielectric Strength on page 17
Attributes
Values
Notes
Signal voltage
Max
35V DC
Voltage between pin 6 and 7
Signal current
Max
10 mA
Voltage drop across opto-coupler
—
0.9V / 3V
At 1 mA / 5 mA while opto-coupler is low ohmic
Leakage current
Max
50 μA
While opto-coupler is high ohmic
Isolation voltage