All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM044A-EN-P — March 2014
27
Bulletin 1606 Switched Mode Power Supplies
23.14. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Recommended
output
current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 23-8
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
INPUT
50
A1
Ambient Temperature
Fig. 23-9
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPU
T
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
A2
Ambient Temperature
A1
Fig. 23-10
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A1
A2
Fig. 23-11
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
IN
PU
T
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A1
A2
Fig. 23-12
Mounting
Orientation E
(Horizontal ccw)
Power Supply
OUTPUT
INPUT
Output Current
0
10
20
30
40
60°C
2.5
5
7.5
10A
50
Ambient Temperature
A1
A2