Allen-Bradley 1606-XLS240E Скачать руководство пользователя страница 27

All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM044A-EN-P — March 2014

27

Bulletin 1606 Switched Mode Power Supplies

23.14. Mounting Orientations

 

Mounting orientations other than input terminals on the bottom and output on the top require a reduction in 
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction 
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous 
operation can be found below: 

Curve A1

 Recommended 

output 

current. 

Curve A2

 

Max allowed output current (results in approximately half the lifetime expectancy of A1). 

 

Fig. 23-8

 

Mounting 
Orientation  A 

(Standard 
orientation)

 

Power

Supply

OUTPUT

 

Output Current

0

10

20

30

40

60°C

2.5

5

7.5

10A

INPUT

50

A1

Ambient Temperature

 

 

 

 

Fig. 23-9

 

Mounting 
Orientation  B 

(Upside down)

 

Power

Supply

OUTPUT

INPU

T

 

Output Current

0

10

20

30

40

60°C

2.5

5

7.5

10A

50

A2

Ambient Temperature

A1

 

 

 

 

Fig. 23-10

 

Mounting 
Orientation  C  

(Table-top 
mounting)

 

 

Output Current

0

10

20

30

40

60°C

2.5

5

7.5

10A

50

Ambient Temperature

A1

A2

 

 

 

 

Fig. 23-11

 

Mounting 
Orientation  D  

(Horizontal cw)

 

Power

Supply

OUTPUT

IN

PU
T

 

Output Current

0

10

20

30

40

60°C

2.5

5

7.5

10A

50

Ambient Temperature

A1

A2

 

 

 

 

Fig. 23-12

 

Mounting 
Orientation  E

  

(Horizontal ccw)

 

Power Supply

OUTPUT

INPUT

 

Output Current

0

10

20

30

40

60°C

2.5

5

7.5

10A

50

Ambient Temperature

A1

A2

 

 

Содержание 1606-XLS240E

Страница 1: ...Increase Output Power 24 23 8 Parallel Use for Redundancy 24 23 9 Daisy Chaining of Outputs 25 23 10 Series Operation 25 23 11 Inductive and Capacitive Loads 25 23 12 Operation on Two Phases 26 23 13...

Страница 2: ...in nearly every environment possible The integrated output power manager a wide range input voltage design and virtually no input inrush current make installation and usage simple Diagnostics are eas...

Страница 3: ...fer to section 24 14 This device is designed for convection cooling and does not require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Ke...

Страница 4: ...92 at 24V 10A see Fig 3 4 Crest factor typ 1 65 1 67 1 85 at 24V 10A Start up delay typ 800ms 650ms 340ms see Fig 3 2 Rise time typ 8ms 8ms 8ms 0mF 24V 10A see Fig 3 2 typ 15ms 15ms 15ms 10mF 24V 10A...

Страница 5: ...e min 88 375Vdc continuous operation DC input current typ 2 37 0 85A 110 300Vdc at 24V 10A All units Allowed Voltage L N to Earth max 375Vdc continuous IEC 62103 Turn on voltage typ 80Vdc steady state...

Страница 6: ...uppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V Inrush current max 10Apeak 10Apeak 10Apeak over entire temperature range typ 5Apeak 4Apeak 7Apeak...

Страница 7: ...r load impedance 100mOhm max 15A continuous load impedance 10mOhm see Fig 6 1 Output capacitance typ 7 000 F included inside the power supply BonusPower short term power capability up to typ 4s The po...

Страница 8: ...h o r t t e r m Adjustment Range Bonus Time 0 110 120 130 140 150 160 1 2 3 7 4 5 6 8 9 10s min max typ Output Power Fig 6 3 BonusPower recovery time Power Demand 100 t t Limitation by Power Manager O...

Страница 9: ...adjusted output voltage level Contact opens As soon as the output voltage dips more than 10 below the adjusted output voltage Short dips will be extended to a signal length of 250ms Dips shorter than...

Страница 10: ...loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest...

Страница 11: ...by the lifetime expectancy of the built in electrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufacturer specification The...

Страница 12: ...5 6mm2 0 5 6mm2 0 5 6mm2 Stranded wire 0 5 4mm2 0 5 4mm2 0 5 4mm2 American Wire Gauge 20 10 AWG 20 10 AWG 20 10 AWG Wire stripping length 10mm 0 4inch 10mm 0 4inch 10mm 0 4inch Screwdriver not applica...

Страница 13: ...DC OK relay contact is synchronized with the DC OK LED See section 8 for details D Output voltage potentiometer Open the flap to adjust the output voltage Factory set 24 1V E DC OK LED green On when...

Страница 14: ...40 of 200Vac 70 of 200Vac 0Vac 20ms 40Vac 200ms 70Vac 500ms 0Vac 20ms 80Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4...

Страница 15: ...al 2 17 8Hz 1 6mm 17 8 500Hz 2g 2 hours axis IEC 60068 2 6 Shock 30g 6ms 20g 11ms 3 bumps direction 18 bumps in total IEC 60068 2 27 Altitude 0 to 2000m 0 to 6 560ft without any restrictions 2000 to 6...

Страница 16: ...current typ 0 19mA 0 44mA 100Vac 50Hz TN TT mains IT mains typ 0 29mA 0 65mA 120Vac 60Hz TN TT mains IT mains typ 0 53mA 1 04mA 230Vac 50Hz TN TT mains IT mains 0 25mA 0 54mA 110Vac 50Hz TN TT mains...

Страница 17: ...60950 1 RECOGNIZED UNDER FILE NUMBER E244404 for use in the U S A UL 60950 1 and Canada C22 2 No 60950 Information Technology Equipment Level 3 ISA 12 12 01 CSA C22 2 No 213 CSA Certified inder File...

Страница 18: ...free of halogens wires and cables are not PVC insulated The production material within our production does not include following toxic chemicals Polychlorized Biphenyl PCB Polychlorized Terphenyl PCT...

Страница 19: ...s run in time unless noted otherwise Rockwell Automation Publication 1606 RM044A EN P March 2014 19 Bulletin 1606 Switched Mode Power Supplies 22 Accessories 22 1 1606 XLB Wall Mounting Bracket This b...

Страница 20: ...ffer Unit s Power Supply Load AC The buffer unit does not require any control wiring It can be added in parallel to the load circuit at any given point Buffer units can be added in parallel to increas...

Страница 21: ...spond with a thermal shut down after a period of time Use the maximum duty cycle curve Fig 23 2 to check if the average output current is below the nominal current Fig 23 1 Repetitive pulse loads defi...

Страница 22: ...current for 5ms typ 10ms DIV Output Voltage Output Current 24V 0A 20A 20 5V Output Voltage 24V Output Current 0A 1ms DIV 50A 14V Peak load 20A resistive for 50ms Output voltage dips from 24V to 20 5V...

Страница 23: ...rotect wires and circuits If the ampere value and the characteristics of the MCB are adapted to the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB open...

Страница 24: ...r system availability Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails The simplest way is to put two power supplies in parallel This i...

Страница 25: ...s for higher output voltages It is possible to connect as many units in series as needed providing the sum of the output voltage does not exceed 150Vdc Voltages with a potential above 60Vdc are no lon...

Страница 26: ...r circuit breakers are specified in section 23 4 External Input Protection 23 13 Use in a Tightly Sealed Enclosure When the power supply is installed in a tightly sealed enclosure the temperature insi...

Страница 27: ...current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 23 8 Mounting Orientation A Standard orientation Power Supply OUTPUT Output Current 0 10 20...

Страница 28: ...getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing fa...

Отзывы: