Rockwell Automation Publication 1606-RM104A-EN-P - July 2020

7

           

AC Input

The device is suitable to be supplied from TN, TT, or IT mains networks with 
AC voltage.

Attributes

Values

Notes

AC input 

Nom

AC 100…240V 

AC input range 

Min 

90…264V AC 

Continuous operation 

Min 

264…300V AC 

Occasionally for 500 ms max

Allowed voltage L or N to earth 

Max 

300V AC 

Continuous, according to IEC 60664-1 

Input frequency 

Nom 

50…60 Hz 

±6% 

Turn-on voltage 

Typ 

81V AC 

Steady-state value, see 

Figure 1

Shut-down voltage 

Typ 

63V AC / 71V AC 

At no load / nom load, steady-state 
value, see 

Figure 1

External input protection 

The device is designed, tested and approved for branch circuits up to 
20 A without additional protection device. For higher branch circuits 
use an additional protection device. If an external input protection 
device is utilized, do not use one smaller than a 10A B- or 6A C-
characteristic to avoid a nuisance tripping of the circuit breaker.

Attributes

Values

Notes

AC 100V 

AC 120V 

AC 230V 

Input current 

Typ 

5.2 A 

4.3 A 

2.3 A 

At 24V, 20 A, see 

Figure 3

 

Power factor 

Typ 

0.99 

0.99 

0.97 

At 24V, 20 A, see 

Figure 4

 

Crest factor 

Typ 

1.6 

1.7 

2.0 

At 24V, 20 A, The crest factor is the 
mathematical ratio of the peak 
value to RMS value of the input 
current waveform. 

Start-up delay 

Typ 

420 ms 

300 ms 

230 ms 

See 

Figure 2

 

Rise time 

Typ 

100 ms 

100 ms 

100 ms 

At 24V, 20 A constant current load, 0 
mF load capacitance, see 

Figure 2

 

Typ 

140 ms 

140 ms 

140 ms 

At 24V, 20 A constant current load, 
20 mF load capacitance, see 

Figure 2

 

Turn-on overshoot 

Max 

200 mV 

200 mV 

200 mV 

See 

Figure 2

Figure 1 - Input voltage range, typ

Figure 2 - Turn-on behavior, definitions

Figure 3 - Input current vs. output load at 24V

Figure 4 - Power factor vs. output load

Turn-on

90V

Rated

input range

max.

500 ms

V

IN

P

OUT

300V AC

264V

Shut

-down

 

Start-up

delay

Rise

Time

Ov

ershoot

- 5%

Output
Voltage

Input
Voltage

 

20 A

0

2.5

5

7.5

10 12.5

15 17.5

0

1

2

3

4

5

6 A

Input Current, typ.

a) 100V AC
b) 120V AC
c) 230V AC

b

a

c

Output Current

 

Power Factor, typ.

2

4

6

8

10 12 14 16 18 20 A

0.75

0.8

0.85

0.9

0.95

1.0

a) 100V AC
b) 120V AC
c) 230V AC

a, b

c

Output Current

 

Содержание 1606-XLB480E

Страница 1: ...Basic Power Supply 24V 20 A 480 W Single phase Input Catalog Number 1606 XLB480E Reference Manual Original Instructions...

Страница 2: ...y Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written per...

Страница 3: ...als 13 Lifetime Expectancy 13 Mean Time Between Failure 13 Electromagnetic Compatibility 14 Environment 15 Safety and Protection Features 16 Dielectric Strength 17 Approvals and Fulfilled Standards 18...

Страница 4: ...4 Rockwell Automation Publication 1606 RM104A EN P July 2020 Table of Contents Notes...

Страница 5: ...monitoring can help to avoid long downtimes Power supply features AC 100 240V Wide range Input Active Power Factor Correction PFC Width only 59 mm 2 32 in Efficiency up to 95 3 Safe HiccupPLUS Overlo...

Страница 6: ...equency 50 60 Hz 6 AC Input current 4 3 2 3 A At 120 230V AC Power factor 0 99 0 97 At 120 230V AC AC Inrush current 15 35 A pk At 120 230V AC 40 C 104 F cold start Efficiency 94 2 95 3 At 120 230V AC...

Страница 7: ...s Notes AC 100V AC 120V AC 230V Input current Typ 5 2 A 4 3 A 2 3 A At 24V 20 A see Figure 3 Power factor Typ 0 99 0 99 0 97 At 24V 20 A see Figure 4 Crest factor Typ 1 6 1 7 2 0 At 24V 20 A The crest...

Страница 8: ...n Attributes Values Notes AC 100V AC 120V AC 230V Inrush current Max 15 A pk 18 A pk 42 A pk At 40 C 104 F cold start Typ 13 A pk 13 A pk 25 A pk At 25 C 77 F cold start Typ 13 A pk 15 A pk 35 A pk At...

Страница 9: ...gulation Max 100 mV Between 0 A and 20 A static value see Figure 7 Ripple and noise voltage Max 100 mVpp Bandwidth 20 Hz to 20 MHz 50 Ohms Output current Nom 20 0 A At 24V and an ambient temperature b...

Страница 10: ...e Figure 9 Min at 24V 10 A 44 ms 44 ms 44 ms See Figure 9 Typ at 24V 20 A 27 ms 27 ms 27 ms See Figure 9 Min at 24V 20 A 22 ms 22 ms 22 ms See Figure 9 Figure 9 Hold up time vs input voltage Figure 10...

Страница 11: ...10 A 25 at 15 A 25 at 20 A Power losses Typ 5 7 W 4 6 W 3 5 W At 24V 0 A Typ 15 6 W 14 8 W 13 2 W At 24V 10 A Typ 32 8 W 29 6 W 23 7 W At 24V 20 A Figure 12 Efficiency vs output current at 24V typ Fig...

Страница 12: ...L N DC OK Contact DC OK Status Indicator DC ok Relay Figure 17 Front side User Elements 1 Input Terminals N L Line input PE Protective Earth input 2 Output Terminals Two identical poles and two identi...

Страница 13: ...s the mean time to failure MTTF value is the same value as the MTBF value Attributes Input Output DC OK Signal Type Screw termination Screw termination Push in termination Solid wire 6 mm2 max 0 0093...

Страница 14: ...EN 61000 4 6 0 15 80 MHz 20V Criterion A Mains voltage dips EN 61000 4 11 0 of 100V AC 0V AC 20 ms Criterion A 40 of 100V AC 40V AC 200 ms Criterion C 70 of 100V AC 70V AC 500 ms Criterion A 0 of 200V...

Страница 15: ...ages 4 kV according to overvoltage category III Input to PE According to IEC 60664 1 for altitudes up to 2000 m 6560 ft Degree of pollution 2 According to IEC 60664 1 not conductive Vibration sinusoid...

Страница 16: ...9 Over temperature protection Included Output shutdown with automatic restart Temperature sensors are installed on critical components inside the unit and turn off the unit in safety critical situatio...

Страница 17: ...he value in the table below We recommend that either the pole or the pole shall be connected to the protective earth system This helps to avoid situations in which a load starts unexpectedly or cannot...

Страница 18: ...Use Particular requirements for control equipment Applicable for US and Canada E File NMTR 7 E56639 Ind Cont Eq Regulation Name Regulation Symbol Notes CE EU Declaration of Conformity Trade conformit...

Страница 19: ...5 mm 0 30 or 0 59 in Housing material Body Aluminum alloy Cover Zinc plated steel Installation clearances 40 mm 1 57 in on top 20 mm 0 79 on the bottom 5 mm 0 20 in left and right side If the adjacent...

Страница 20: ...d even if there is a short circuit across the output It requires suitable power supplies on the input where the sum of the continuous short circuit current stays below 26 A This is typically achieved...

Страница 21: ...ncrease the output ampacity or the hold up time For longer hold up times the 1606 XLSBUFFER24 might also be an option Series Operation Devices of the same type can be connected in series for higher ou...

Страница 22: ...bient temperatures up to 70 C 158 F Leakage current EMI inrush current and harmonics increase when using multiple devices Recommendations for building redundant power systems Use separate input fuses...

Страница 23: ...d in the middle of the box no other heat producing items are inside the box The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1 cm...

Страница 24: ...24 Rockwell Automation Publication 1606 RM104A EN P July 2020 Notes...

Страница 25: ...and dispose of equipment Industrial Components Preventive Maintenance Enclosures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial a...

Страница 26: ...Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation inst...

Отзывы: