Rockwell Automation Publication 1606-RM104A-EN-P - July 2020
15
Environment
Switching Frequencies
PFC converter
80...130 kHz
Input voltage and load dependent
Main converter
75...180 kHz
Output voltage and load dependent
Auxiliary converter 60 kHz
Fixed frequency
Attributes
Values
Notes
Operational temperature
-25…+70 °C (-13…+158 °F)
Operational temperature is the same as the ambient or surrounding
temperature and is defined as the air temperature 2 cm (0.79 in.)
below the unit.
Storage temperature
-40…+85 °C (-40…+185 °F)
For storage and transportation
Output derating
12 W/°C (12 W/1.8 °F),
30 W/1000 m (30 W/3281 ft),
or 5 °C/1000 m (9 °F/3281 ft)
Between 55…70 °C (131…140 °F)
For altitudes >2000 m (6560 ft), see
The derating is not hardware-controlled. You have to take this into consideration to stay below the
derated current limits in order not to overload the unit.
Humidity 5...95%
r.h. According to IEC 60068-2-30
Atmospheric pressure
110…54 kPa
See
for details
Altitude
Up to 5000 m (16,400 ft)
for details
Overvoltage category
II
According to IEC 60664-1, for altitudes up to 5000 m (16,400 ft)
Impulse withstand voltages
4 kV (according to overvoltage
category III)
Input to PE According to IEC 60664-1, for altitudes up to 2000 m
(6560 ft)
Degree of pollution
2
According to IEC 60664-1, not conductive
Vibration sinusoidal
2…17.8 Hz: ±1.6 mm (0.06 in.);
17.8…500 Hz: 2 g (19.61 m/s
2
)
2 hours / axis
According to IEC 60068-2-6
Shock
30 g 6 ms, 20 g 11 ms
3 bumps per direction,
18 bumps in total
According to IEC 60068-2-27
Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15
mm (0.59 in.) and a thickness of 1.3 mm (0.05 in.) and standard orientation.
LABS compatibility
As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is
suitable for use in paint shops.
Corrosive gases
Tested according to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a
service life of 10 years min in these environments.
Audible noise
Some audible noise may be emitted from the power supply during no load, overload, or short circuit.
Figure 18 - Output current vs. ambient temp.
Figure 19 - Output current vs. altitude
0
0
+70 °C
20 A
+55
Allowed Output Current at 24V
12.5 A
Ambient Temperature
-25
2000 m
5000 m
18.8 A
16.3 A
20.0 A
Altitude
Allowed Output Current at 24V
B
A
AP
*)
80 kPa
54 kPa
110 kPa
0 m
*) Atmospheric pressure
A... Tamb < 45 °C
B... Tamb < 55 °C
4000 m
62 kPa