Chapter 4 Maintenance
Door Interlock
Circumvention
Some of the following sections may require moving the isolation switch handle
to the ON position while the medium voltage door is open. The interlocking
safeguards in the mechanism are designed to prevent the handle from moving
to the ON position while the cabinet door is open.
•
To circumvent this safety feature, use a screwdriver, or other tool, to
depress the door interlock lever in a downward movement.
•
Hold the lever down while moving the handle to the ON (closed) position.
Figure 46 - Door Interlock Lever
ATTENTION:
The door interlock mechanism is designed to prevent
access to the medium voltage cell while the unit is energized. When the
unit is in operation, do not circumvent this interlocking safety feature.
Always disconnect and lock out incoming power (refer to
) before proceeding with any adjustments
requiring the handle to be moved to the ON (closed) position. Failure to
do so may result in electric shock causing severe burns, injury or death.
Door Interlock Lever
ATTENTION:
Use suitable personal protective equipment (PPE) per
local codes or regulations. Failure to do so may result in severe burns,
injury or death.
ATTENTION:
Always perform the Power Lock-out procedure before
servicing the equipment. Failure to do so may result in severe burns,
injury or death.
Содержание 1512B
Страница 6: ...6 Rockwell Automation Publication 1500 UM055I EN P December 2021 Notes...
Страница 74: ...74 Rockwell Automation Publication 1500 UM055I EN P December 2021 Chapter 4 Maintenance Notes...
Страница 76: ...76 Rockwell Automation Publication 1500 UM055I EN P December 2021 Chapter 5 Spare Parts Notes...
Страница 106: ...106 Rockwell Automation Publication 1500 UM055I EN P December 2021 Appendix E History of Changes Notes...