Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
35
Install the Dynamix 1444 Series Monitoring System
Chapter 2
Use solid or stranded wire. All wiring must meet the following specifications:
• Minimum insulating rating of 300V
• You are not allowed to solder the conductor
• Wire ferrules can be used with stranded conductors; copper ferrules
recommended
• Single wire per connection
Removable Connector Keyring
Each terminal block on each module is numbered with its corresponding pin
numbers, which match the pin numbers on its Removable Plug Connector
(RPC). Additionally, each terminal block on each module and base also
includes two keys that make sure that only its matching RPC can be plugged
into it. However, with sufficient force it is possible to defeat the keys. If the keys
are defeated, then when the RPC is later removed it is possible that the key
becomes dislodged from its pin location.
If a key is removed from its connector, it isn’t necessary to replace it as it only
serves to help match the RPC to its connector. However, the key can be readily
inserted back into its connector. When doing so, make sure that the key is
placed into the correct pin location as shown in
Table 5 - RPC Pin Numbers and Key Locations
Catalog Number
Description
Terminal
RPC Catalog
Number
(1)
(1) Each RPC includes two connectors, each numbered and keyed to match either the upper or lower terminal connector of the
module or base that it is associated with.
Pin
Numbers
Key
Locations
1444-DYN04-01RA
Dynamic
Measurement Module
Upper
1444-DYN-RPC-xxx-01
33…48
34, 47
Lower
1…16
3,14
1444-TSCXO2-02RB
Tachometer Signal
Conditioner
Expansion Module
Upper
1444-TSC-RPC-xxx-01
13…18
16, 17
Lower
1…6
2, 6
1444-RELX00-04RB
Relay Expansion
Module
Upper
1444-REL-RPC-xxx-01
13…18
13, 17
Lower
1…6
3, 5
1444-AOFX00-04RB
4-20mA Expansion
Module
Upper
1444-AOF-RPC-xxx-01
13…18
14, 16
Lower
1…6
2, 5
1444-TB-A
Terminal Base for
1444-DYN04-01RA
Upper
1444-TBA-RPC-xxx-01
49…64
49, 64
Lower
17…32
20, 29
1444-TB-B
Terminal Base for
1444 Series Expansion
Modules
Upper
1444-TBB-RPC-xxx-01
19…24
21, 24
Lower
7…12
7, 10
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......