Allen-Bradley 140MG-H Скачать руководство пользователя страница 2

 Green

 L

 Red

LED Fully illuminated = L pre alarm (0.9   I1 < I < 1.2  I1)

LED Flashing =  Overcurrent fault (I > 1.2 I1)

U

 Red

L | U |  I

 Red

LED Flashing = Trip Coil disconnected

 LED

 Color

CONDITION  Run time

LED Flashing = Phase Unbalance

t6

I6

and

3E

2s<ti<3s

5E

3s<ti<5s

 @ (7.2 x I1)

10E

5s<ti<10s

20E

10s<ti<20s

In = 100 A
I1 = 100 x (0.4+0.08+0.32)= 80A
CLASS = 3E@(7.2xI1)=2s<ti<3s@576A(7.2Ax80)

Example:

I3

 =100 x (6+1+2)=900A

In=100 A

Settaggio di default
Default-Einstellung
Configuration par défauit 
Ajuste de default 

Example:

t

L

CLASS

I

I3

I1

I

U

t

L

CLASS

I

I3

I1

I

U

min  (L1, L2, L3) < 0.1In

 

max (L1, L2, L3) > 0.5 I1

I6=

{

 U = ON
 

t

L

CLASS

I

I3

I1

I

U

2

  
  t6 = 2s 

1

(2)

2

M-LIU

Default setting

DIR 1000721R0507 Version 04

140G-ELTT is required for fault identification in compliance with UL508A